User Manual (e-shelter)
Figure 3-23 Removing the connecting copper bars
Step 5 Connect a ground cable to the UPS.
If you do not ground the UPS as required, electromagnetic interference, electric shocks, or fire
may occur.
Connect cables from top to bottom in this sequence: mains input power cables, output
power cables, bypass input power cables, and battery input cables.
When connecting cables, tighten bolts from inside out to secure cables.
Before cable connections, ensure that all UPS input switches are OFF. Paste warning
labels to prevent operation on the switches.
Connect input power cables to the UPS and then to customer equipment.