UPS5000-A-500 kVA
User Manual (e-shelter)
Item
Frequency
Total harmonic
distortion of
output voltage
(THDv)
Output PF
Transfer time
Output voltage
unbalance
Overload
capability
Table 8-9 System Electrical Specifications
Item
Redundancy design
ECO
Issue 02 (2020-01-10)
Parameters
In normal mode, the mains frequency is synchronous with the
bypass input frequency.
In battery mode, the frequency is 50 Hz or 60 Hz (tolerance
± 0.05%).
THDv ≤ 1% at rated input voltage and 100% linear load
THDv ≤ 4% at rated input voltage and 100% non-linear load
1
0 ms (uninterruptible transfer)
≤ 20 ms (interruptible transfer)
Voltage unbalance: ± 3%; phase unbalance: 120± 2°
Inverter overload capability:
100% < load ≤ 110%: transfer to bypass mode after 60 min
110% < load ≤ 125%: transfer to bypass mode after 10 min
125% < load ≤ 150%: transfer to bypass mode after 1 min
Load > 150%: transfer to bypass mode after 200 ms
Bypass overload capability:
At 30°C, load ≤ 135%: long-time operation
At 40°C, load ≤ 125%: long-time operation
load > 1000% : run for 100 ms