4.3.2

Input Power Failure

During an Input Power Failure, the UPS inverter will be powered by the Energy Storage System. The following will be
displayed on the main and measurement screen.

Figure 4-14 Main Screen (Battery Operation)

The LCD will display a battery low voltage message when the battery capacity is near depletion. The End of Battery
Discharge announcement is displayed when the battery end voltage is reached. At this time, the inverter will perform
an electronic shutdown to prevent battery loss of life typical from extreme deep discharge conditions. When the input
power is restored, in a single UPS module system, the inverter will automatically restart to power the load, and the
batteries will be simultaneously recharged. Manual restart will be required in a multi-module system (MMS). The End
of Battery announcement is shown at the bottom of the screen.
4.3.3

Fault Indication

"MESSAGE" and "SILENCE ALARM" icons will appear on the main menu when UPS failure condition has occurred.
The following will be displayed when the MESSAGE icon on the main menu is pressed.
26

Figure 4-16 Main Screen (Fault Indication)

G2020 Series UPS Installation and Operation Manual – 94861-004

Figure 4-15 Measurement Screen (Battery Operation)