Toshiba nv Series Instruction Manual page 37

Controller unit
Hide thumbs Also See for nv Series:
Table of Contents

Advertisement

(2) For base unit BU825:
PS-A power module 25A>
(A0 slot consumption current +
A2 slot consumption current +
A3 slot consumption current +
A4 slot consumption current +
A5 slot consumption current +
A6 slot consumption current)
and
PS-B power module 25A>
(B0 slot consumption current +
B2 slot consumption current +
B3 slot consumption current +
B4 slot consumption current +
B5 slot consumption current +
B6 slot consumption current)
Configure the system so that the total of the consumption current satisfies the
capacity of the power using the list of current consumptions and weights by
module shown in the table of Appendix A.6 according to the DC24V power
capacity used for the power consumption and output power of TC-net I/O
modules.
Table 1-8 List of module consumption current
Name
Model
Power unit
PU811
type1
PU811A
type1
PU821
type2
PU821A
type2
Station bus
EN811
General-purpose GB/100MB
module
(Electricity single)
FN812
OIS-DS connection GB/100MB
(Electricity duplex)
TN821
TC-net 100 (Optical, single)
TN821A
TC-net 100 (Optical, single)
TN822
TC-net 100 (Optical , duplex)
TN822A
TC-net 100 (Optical , duplex)
Internal 5V
consumption
Brief description
(Maximum)
6A
6A
6A
6A
2A
2A
2A
2A
2A
2A
Unified Controller nv series Controller Unit Instruction Manual
1.4 Installation Condition
Weight
current
(about)
800g
800g
800g
800g
500g
500g
500g
500g
500g
500g
19