Functions

7.1 Preconditions for burner startup

Burner control must be reset
All contacts in the line are closed, request for heat
No undervoltage
Air pressure switch or CPI must be in its no-load position, or DBR2 is connected
Fuel valve 1 is connected
Fan motor or AGK25 is connected
Flame detector is darkened and there is no extraneous light

7.2 Undervoltage

Safety shutdown from the operating position takes place should mains voltage drop
below about AC 75 V (at UN = AC 120 V)
Restart is initiated when mains voltage exceeds about AC 95 V (at UN = AC 120 V)
Safety shutdown from the operating position takes place should mains voltage drop
below about AC 165 V (at UN = AC 230 V)
Restart is initiated when mains voltage exceeds about AC 175 V
(at UN = AC 230 V)

7.3 Controlled intermittent operation

After no more than 24 hours of continuous operation, the burner control initiates
automatic controlled shutdown followed by a restart.
Basic Documentation LME39...
7 Functions
CC1P7106en
08.12.2017