GOT2000 series automatic recognition

• When the GOT2000 series is connected, the parameters required for the GOT connection are automatically changed by
setting the automatic recognition on the GOT2000 series side.
• Set the station number (Pr.331) of the inverter before the automatic recognition is performed.
• Connect all the stations of inverters with GOT before the automatic recognition is performed. The inverter newly added after
automatic recognition will not be recognized automatically. (When an inverter is added, perform the initial setting in Pr.999
Automatic parameter setting or set the automatic recognition on the GOT side again.)
Automatic change item
Communication speed
Data length/stop bit
Parity
Waiting time setting
CR/LF selection
Number of communication retries
Communication check time interval
Protocol selection
NOTE
• If the automatic recognition cannot be performed, initial setting in Pr.999 is required.
• For connection to a device other than the GOT2000 series, initial setting in Pr.999 is required.
• For details, refer to the GOT2000 Series Connection Manual (Mitsubishi Product).
Automatic change
parameter
Pr.332
Pr.333
Depending on the setting of the
Pr.334
connected device on the GOT side.
Pr.337
Pr.341
Pr.335
9999 (fixed)
Pr.336
9999 (fixed)
Pr.549
0 (fixed to Mitsubishi inverter protocol)
Setting value after change
89
PARAMETER