4.5.7

Preset Single Register (writing of data to holding registers) (H06 or 06)

• The content of the "system environmental variables" and "inverter parameters" assigned to the holding register area (refer to
the register list
(page
78)) can be written.
• Query message
a. Slave Address
b. Function
H06
(8 bits)
(8 bits)
• Normal response (Response message)
a. Slave Address
b. Function
H06
(8 bits)
(8 bits)
• Query message setting
Message
a
Slave Address
b
Function
c
Register Address
d
Preset Data
70
PARAMETER
c. Register Address
H
L
H
(8 bits)
(8 bits))
(8 bits)
c. Register Address
H
L
H
(8 bits))
(8 bits)
(8 bits)
Set the address to send messages to. Setting "0" enables broadcast communication.
Set H06.
Set the address from data is written to the holding register.
Register address = holding register address (decimal) - 40001
For example, when register address 0001 is set, data is written to holding register
address 40002.
Set the data to write to the holding register. Write data is fixed at 2 bytes.
d. Preset Data
CRC Check
L
L
(8 bits)
(8 bits)
d. Preset Data
CRC Check
L
L
(8 bits)
(8 bits)
Description
H
(8 bits)
H
(8 bits)