Mitsubishi Electric 800 Series Instruction Manual page 26

Rs-485 interface board, rs-485 communication terminals
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement


Follows the Pr.338 Communication operation command source and Pr.339 Communication speed command source settings.
(Refer to the Instruction Manual (Detailed) of the inverter.)

At occurrence of RS-485 communication error, the inverter cannot be reset from the computer.

PU stop is only enabled. PS is displayed on the operation panel during PU stop. Follows the Pr.75 Reset selection/disconnected PU
detection/PU stop selection setting. (Refer to the Instruction Manual (Detailed) of the inverter.)

Writing of some parameters may be disabled by the Pr.77 Parameter write selection setting and the operating condition. (Refer to the
Instruction Manual (Detailed) of the inverter.)

Some parameters are write-enabled independently of the operation mode and command source presence/absence. Writing is also
enabled when Pr.77="2". (Refer to the Instruction Manual (Detailed) of the inverter.) Parameter clear is disabled.

When Pr.550 NET mode operation command source selection="1" (RS-485 terminals enabled), or Pr.550 NET mode operation
command source selection="9999" with no communication option connected.

When Pr.550 NET mode operation command source selection="0" (communication option enabled), or Pr.550 NET mode operation
command source selection="9999" with communication option connected.