A.2. Combustible (LEL), IR, Cat-bead Sensor Specifications
Table A-2: Combustible (LEL), IR, Cat-bead Sensor Specifications
Category
Specifications
IR - Combustible (LEL) Sensor
Default Range
0 to 100% LEL
Accuracy
50%LEL and below:
>50%LEL:
Warm Up Time
30 Mins.
Response Time
T90 <20Sec
Operating Temp.
-40.0 to +167°F (-40 to +75°C)
Storage Temp.
-67.0 to +167°F (-55 to +75°C)
Humidity
0 to 95% RH, Non-Condensing
Default Cal Gas
CH
4
IR - Carbon Dioxide (CO
Default Range
0-5% V/V
Accuracy
+ 0.25%V/V
Warm Up Time
30 Mins.
Response Time
T90 <30Sec
(w/optional
deluge guard)
Operating Temp.
-40.0 to +167°F (-40 to +75°C)
Storage Temp.
-4.0 to +122°F (-55 to +75°C)
Humidity
0 to 95% RH, Non-Condensing
Default Cal Gas
CO
2
Cat-Bead - Combustible (LEL) Sensor
Default Range
0-100%LEL
Accuracy
<50%LEL:
>50%LEL:
Warm Up Time
5 Mins.
Response Time
T90 <20Sec
Information contained herein is classified as EAR99 under the U.S. Export Administration Regulations. Export, reexport or diversion contrary to U.S. law is