Table 7-1 Eventlist
Code
Name
ID001
GridOVP
ID002
GridUVP
ID003
GridOFP
ID004
GridUFP
ID005
GFCI
ID006
OVRT fault
ID007
LVRT fault
ID008
IslandFault
ID009
GridOVPInstant1
ID010
GridOVPInstant2
HYD 10-20KTL-3PH
Description
The grid voltage is too
high
The grid voltage is too
low
The grid frequency is
too high
The grid frequency is
too low
Charge Leakage Fault
OVRT
function
faulty
LVRT function is faulty
Island protection error
Transient
overvoltage
of grid voltage 1
Transient
overvoltage
of grid voltage 2
- 49 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
If the alarm occurs occasionally, the
possible cause is that the electric grid is
abnormal
occasionally.
automatically return to normal operating
status when the electric grid's back to
normal.
If the alarm occurs frequently, check
whether the grid voltage/frequency is within
the acceptable range. If yes, please check
the AC circuit breaker and AC wiring of the
inverter.
If the grid voltage/frequency is NOT within
the acceptable range and AC wiring is
correct, but the alarm occurs repeatedly,
contact technical support to change the grid
over-voltage,
over-frequency, under-frequency protection
points after obtaining approval from the
local electrical grid operator.
is
Internal faults of inverter, switch OFF
inverter, wait for 5 minutes, then switch ON
inverter. Check whether the problem is
solved.
If no, please contact technical support.