Sofar solar HYD 10K-20KTL-3PH User Manual page 47

Energy storage integrated inverter
Table of Contents

Advertisement

3)
If PV generation < LOAD consumption
(ΔP > 100W), inverter will discharge
battery.
6.3.2 Advanced setting
2.Advanced setting
1. Battery Parameter
1.Battery
OK
Parameter
Depth of Discharge
For example: if Discharge Depth = 50% & EPS Discharge Depth = 80%.
While grid is connected: Inverter won't discharge the battery when its SOC
is less than 50%.
HYD 10-20KTL-3PH
OK
1.Battery Number
2.Battery Address
3.Protocol
4.Max Charge Curr Limit
5.Max DisChg Curr Limit
*6.Depth of Discharge
Copyright © Shenzhen SOFARSOLAR Co., Ltd
4)
If PV generation is normal,but LOAD
consumption=0, the surplus power will be
stored in the battery.
Input 0715
1.Battery Parameter
2.Clear Energy Data
3.Clear Events
4.Country
5.Anti Reflux
6.IV Curve Scan
7.Logic interface Control
8.Safety Param
7.End of Discharge
8.Capacity
9.Nominal Bat Voltage
10.Cell Type
11.Save
- 42 -