Cautions On Wired Control Replacement - Gree Ultra Heat GMV Multi VRF Heat Pump Series Service Manual

Table of Contents

Advertisement

Ultra Heat GMV VRF Technical Service Manual
TIP: If there are N units within the network, the units should be numbered from N+1.
Special situation:
In some cases, the created project number is identical to that of a unit within the network. In this
case, you can use the ―one-key IDU project number reset‖ function. However, this function will
cause the project number of the entire system to be re-distributed; thus, original number will be
changed. If you do not expect this result, forbid the use of this function and replace the AP1 again.
Methods to use the ―one-key IDU project number reset‖ function:
Method 1: If the IDU is configured with wired control, set P45 to reset IDU project number through
one key function.
Method 2: If the IDU is configured with lamp board, use the special control YV1L1 to set P45 and
reset IDU project number through one key function.
Method 3: On the AP1 of the master ODU, press and hold SW5 for 10 seconds at least to clear all
project numbers of the IDUs and then redistribute project numbers. Other parameters are kept
unchanged.
After replacing the main board of master indoor unit, the master indoor unit must be reset.
1.1.4 Cautions on replacement of slave IDU AP1
If the AP1 of a slave IDU needs to be replaced, after it is powered on, ―Project number conflict
(C5)‖ alarm may be reported. Refer to section 2.3 ―Cautions on Replacement of Master IDU AP1‖ to
address the issue.

1.2 Cautions on Wired Control Replacement

1.2.1 Cautions on wired control XK46 replacement
(1) If the wired control to be replaced controls only one IDU, directly replace the control.
(2) If the wired control to be replaced controls multiple IDUs, perform the steps below first:
Set the wired control parameter ―P14‖ to change the number of managed IDUs to the actual
quantity the control manages. For example, if the wired control manages 3 IDUs, set this parameter to 3.
If you keep the default value 1, the LCD displays L9 (as shown in the figure below).
(3) If there are two wired controls controlling one or multiple IDUs, perform the steps below first:
Set the wired control parameter ―P13‖ to change the address of one control to 01 (master) and that
of the other control to 02 (slave); otherwise, a CP (multiple master wired controls) fault alarm will be
reported (as shown in the figure below).
125
MAINTENANCE

Advertisement

Table of Contents
loading

Table of Contents