Unit Operating Temperature - Gree Ultra Heat GMV Multi VRF Heat Pump Series Service Manual

Table of Contents

Advertisement

Ultra Heat GMV VRF Technical Service Manual
If the above equation cannot be satisfied, then follow the following steps.
 Selection of air conditioning system: select one of the next
(1) Installation of effective opening part
(2) Reconfirmation of Outdoor Unit capacity and piping length
(3) Reduction of the amount of refrigerant
(4) Installation of 2 or more security device (alarm for gas leakage)
 Change Indoor Unit type:
Installation position should be over 6.6ft from the floor (Wall mounted type → Cassette type)
 Adoption of ventilation system:
Choose ordinary ventilation system or building ventilation system
 Limitation in piping work:
Prepare for earthquake and thermal stress

8 UNIT OPERATING TEMPERATURE

Cooling
Heating
NOTICE! Out of the working Temperature Range may damage this products and will invalidate the
warranty.
Electrify the unit 8 hours before operation. Please switch on for 8 hours before operation. Do not cut
off the power when 24 hours short-time halting (to protect the compressor).
 If unit operates out of the above range, it may not work stably and components may even be
damaged.
Ambient temperature: -10º C(14º F)~52º C(125.6º F)
Ambient temperature: -30º C (-22º F)~24º C (75.2º F)
16