The X2200M uses a sensor that has a broader spectrum than the standard sensor. It is designed to detect fires with
unusual chemistry such as black powder. Consult factory for usage recommendations.
X2200M RESPONSE CHARACTERISTICS
High Sensitivity
Fuel
Size
Black Powder
40 grams
X2200M RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARMS
High Sensitivity (Standard Mode)
False Alarm Source
Sunlight, direct, reflected, modulated & unmodulated
70 w sodium vapor lamp, modulated & unmodulated
250 w vapor lamp, modulated & unmodulated
300 w incandescent lamp, modulated & unmodulated
500 w halogen lamp, modulated & unmodulated
1500 w electric radiant heater, modulated & unmodulated
2-34 w fluorescent lamps, modulated & unmodulated
X2200M FALSE ALARM IMMUNITY
High Sensitivity (Standard Mode)
False Alarm Source
Sunlight, direct, reflected
70 w sodium vapor lamp
250 w vapor lamp
300 w incandescent lamp
500 w halogen lamp
1500 w electric radiant heater
2-34 w fluorescent lamps
8.3
FM Approval and Performance Report – Continued
Distance
Typical Response Time
feet (m)
(seconds)
10 (3)
0.1
Distance
feet (m)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
Mode
Standard
Distance
Fire Source
feet (m)
2-inch dia n-Heptane
3 (0.9)
1 x 1 foot n-Heptane
3 (0.9)
1 x 1 foot n-Heptane
3 (0.9)
1 x 1 foot n-Heptane
3 (0.9)
1 x 1 foot n-Heptane
10 (3)
1 x 1 foot n-Heptane
3 (0.9)
1 x 1 foot n-Heptane
Modulated Response
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
24
Typical
Distance
Response Time
feet (m)
(seconds)
10 (3)
<15
40 (12)
0.1
40 (12)
0.1
40 (12)
0.1
40 (12)
0.1
40 (12)
0.1
40 (12)
0.1
Unmodulated Response
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
95-8549