UTC Fire and Security Det-Tronics X2200 Instructions Manual page 13

Uv flame detector
Table of Contents

Advertisement

EQP Model
1. Connect external wires to the appropriate terminals
inside the device junction box. (See Figure 13 for
terminal identification.)
2. Connect the shield of the power cable to "earth
ground" at the power source.
3. Connect shields for the LON cable as indicated. See
Figure 14.
DO NOT ground any shields at the detector
housing.
4. Set the device network address. (See "Setting
Device Network Addresses" section of this manual
for switch setting procedure.)
8.3
NOTE
COM SHIELD
COM 1 A
COM 1 B
POWER SHIELD
+
24 VDC
24 VDC
Figure 13—Wiring Terminal Identification for X2200 EQP Model
5. Check all field wiring to be sure that the proper
connections have been made.
6. Replace the device cover.
7. Make the final sighting adjustments and ensure that
the mounting bracket hardware is tight.
Refer to the Eagle Quantum Premier system manual
(number 95-8533) for information regarding power
and network communication cable requirements.
6
16
COM SHIELD
5
15
COM 2 A
4
14
COM 2 B
3
13
POWER SHIELD
2
12
+
24 VDC
1
11
24 VDC
11
NOTE
A2089
95-8549