100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A
GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF
INCIDENCE DECREASES.
VIEWING ANGLE
15°
30°
45°
DETECTION
DISTANCE
(PERCENT)
A1288
Figure 18—Detector Cone of Vision
CONE OF VISION—
The detector has a 90° cone of vision (horizontal) with
the highest sensitivity lying along the central axis.
See Figure 18.
RESPONSE TIME—
Less than 6 seconds. (See Appendix A for details.)
4.7
(11.9)
B2223
8.3
15°
100
30°
90
80
70
60
50
40
30
20
10
10.2
(25.9)
Figure 19—Dimensions in Inches (cm)
ENCLOSURE MATERIAL—
Copper-free aluminum (painted) or 316 stainless steel.
VIBRATION—
Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW).
DIMENSIONS—
See Figure 19.
45°
WIRING—
Field wiring screw terminals are UL/CSA rated for up to
14 AWG wire, and are DIN/VDE rated for 2.5 mm
Screw terminal required torque range is 3.5–4.4 in.-lbs.
(0.4-0.5 N·m).
14 AWG (2.08 mm
cable is recommended.
Important: 18 Vdc minimum must be available at the
detector. For ambient temperatures below
–10°C and above +60°C use field wiring
suitable for both minimum and maximum
ambient temperature.
THREAD SIZE—
Conduit connection: Four entries, 3/4 inch NPT or M25.
Conduit seal not required.
SHIPPING WEIGHT (Approximate)—
Aluminum:
6 pounds (2.75 kilograms).
Stainless Steel: 10 pounds (4.5 kilograms).
Swivel Mount (AL): 6 pounds (2.75 kilograms).
Swivel Mount (SS): 14 pounds (6.4 kilograms).
WARRANTY PERIOD—
3 years.