THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS DESCRIBE THE FM APPROVAL:
Explosion-proof for Class I, Div. 1, Groups B, C and D (T5) Hazardous (Classified) Locations per FM 3615.
Dust-ignition proof for Class II/III, Div. 1, Groups E, F and G (T5) Hazardous (Classified) Locations per FM 3615.
Nonincendive for Class I, Div. 2, Groups A, B, C and D (T3) Hazardous (Classified) Locations per FM 3611.
Nonincendive for Class II, Div. 2, Groups F and G (T3) Hazardous (Classified) Locations per FM 3611.
Enclosure rating NEMA Type 4X per NEMA 250.
Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C).
Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000).
The following performance criteria were verified:
OPTICAL INTEGRITY TEST:
The detector generated an optical fault in the presence of contamination on any single or combination of lens surfaces
resulting in a loss of approximately 50% of its detection range, verifying that the detector performs a calibrated
Automatic Optical Integrity (o i ) test for each sensor. Upon removal of the contamination, the detector fault was cleared
and the detector was verified to detect a fire.
The Manual / Magnetic o i performs the same calibrated test as the Automatic o i , and additionally actuates the alarm
relay to verify output operation. If there is a 50% loss of its detection range, an alarm signal is not generated.
RESPONSE CHARACTERISTICS
Very High Sensitivity
Fuel
Size
n-Heptane
1 x 1 foot
Methane
32 inch plume
High Sensitivity
Fuel
Size
n-Heptane
1 x 1 foot
n-Heptane
1 x 1 foot
n-Heptane
1 x 1 foot
Methane
32 inch plume
Methane
32 inch plume
Methane
32 inch plume
Medium Sensitivity
Fuel
Size
n-Heptane
1 x 1 foot
n-Heptane
1 x 1 foot
Methane
1 x 1 foot
Methane
32 inch plume
*Add 2 seconds for EQP Model.
8.3
APPENDIX A
FM Approval and Performance Report
Distance
Typical Response Time
feet (m)
(seconds)*
85 (25.9)
3
100 (30.5)
2
Distance
Typical Response Time
feet (m)
(seconds)*
60 (18.3)
2
60 (18.3)
2
60 (18.3)
7
70 (21.3
2
70 (21.3
2
70 (21.3
2
Distance
Typical Response Time
feet (m)
(seconds)*
35 (10.6)
2
50 (15.2)
3
55 (16.8)
2
55 (16.8)
2
Mode
Low Arc
Low Arc
Mode
Standard
Hi Arc
Very Hi Arc
Standard
Hi Arc
Very Hi Arc
Mode
Standard
Hi Arc
Standard
Hi Arc
21
95-8549