FEATURES
•
Responds to a fire in the presence of modulated
blackbody radiation (i.e. heaters, ovens, turbines)
without false alarm.
•
High speed capability.
•
Built-in data logging / event monitoring, up to 1500
events (up to 1000 general, 500 alarms).
•
Automatic, manual or magnetic optical integrity (o i )
testing.
Easily replaceable o i plate.
•
•
Fire, fault and auxiliary relays standard.
•
0 to 20 mA isolated output (optional).
•
Eagle Quantum Premier LON/SLC output (optional).
•
A tricolor LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
or fault conditions.
•
Operates under adverse weather conditions.
•
Mounting swivel allows easy sighting.
•
Integral wiring compartment for ease of installation.
•
Explosion-proof/flame-proof detector housing. Meets
FM, CSA, ATEX and CE certification requirements.
•
Class A wiring per NFPA-72.
• Meets NFPA-33 response requirement for under
0.5 second (available when model selected).
•
3 year warranty.
•
Advanced signal processing (ARC).
•
RFI and EMC Directive compliant.
ASSOCIATED MANUALS
List of X2200 related manuals:
TITLE
Pulse
EQP
HART Addendum
8.3
FORM NUMBER
95-8552
95-8533
95-8638
SPECIFICATIONS
OPERATING VOLTAGE—
24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum).
Maximum ripple is 2 volts peak-to-peak.
POWER CONSUMPTION—
2.5 watts at 24 Vdc nominal;
4.5 watts at 24 Vdc in alarm.
2.8 watts at 30 Vdc nominal;
5.1 watts at 30 Vdc in alarm.
Total power:
7.6 watts at 30 Vdc with EOL resistor
installed.
EOL resistor must be ceramic, wirewound type, rated
5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
For HART model, refer to Addendum number 95-8638.
POWER UP TIME—
Fault indication clears after 0.5 second; device is ready
to indicate an alarm condition after 30 seconds.
OUTPUT RELAYS—
Fire Alarm relay, Form C, 5 amperes at 30 Vdc:
The Fire Alarm relay has redundant terminals
and normally open / normally closed contacts,
normally de-energized operation, and latching or
non-latching operation.
Fault relay, Form A, 5 amperes at 30 Vdc:
The Fault relay has redundant terminals and
normally open contacts, normally energized
operation, and latching or non-latching operation.
Auxiliary relay, Form C, 5 amperes at 30 Vdc:
The auxiliary relay has normally open / normally
closed contacts, normally energized or de-energized
operation, and latching or non-latching operation.
CURRENT OUTPUT (Optional)—
0 to 20 milliampere (±0.3 mA) dc current, with a
maximum loop resistance of 500 ohms from 18 to
19.9 Vdc and 600 ohms from 20 to 30 Vdc.
LON OUTPUT—
Digital communication, transformer isolated (78.5 kbps).
TEMPERATURE RANGE—
Operating:
–40°F to +167°F (–40°C to +75°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
Hazardous location ratings from –55°C to +75°C available
on flameproof model.
HUMIDITY RANGE—
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.
16
95-8549