Features; Specifications - UTC Fire and Security Det-Tronics X2200 Instructions Manual

Uv flame detector
Table of Contents

Advertisement

FEATURES

Responds to a fire in the presence of modulated
blackbody radiation (i.e. heaters, ovens, turbines)
without false alarm.
High speed capability.
Built-in data logging / event monitoring, up to 1500
events (up to 1000 general, 500 alarms).
Automatic, manual or magnetic optical integrity (o i )
testing.
Easily replaceable o i plate.
Fire, fault and auxiliary relays standard.
0 to 20 mA isolated output (optional).
Eagle Quantum Premier LON/SLC output (optional).
A tricolor LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
or fault conditions.
Operates under adverse weather conditions.
Mounting swivel allows easy sighting.
Integral wiring compartment for ease of installation.
Explosion-proof/flame-proof detector housing. Meets
FM, CSA, ATEX and CE certification requirements.
Class A wiring per NFPA-72.
• Meets NFPA-33 response requirement for under
0.5 second (available when model selected).
3 year warranty.
Advanced signal processing (ARC).
RFI and EMC Directive compliant.
ASSOCIATED MANUALS
List of X2200 related manuals:
TITLE
Pulse
EQP
HART Addendum
8.3
FORM NUMBER
95-8552
95-8533
95-8638

SPECIFICATIONS

OPERATING VOLTAGE—
24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum).
Maximum ripple is 2 volts peak-to-peak.
POWER CONSUMPTION—
2.5 watts at 24 Vdc nominal;
4.5 watts at 24 Vdc in alarm.
2.8 watts at 30 Vdc nominal;
5.1 watts at 30 Vdc in alarm.
Total power:
7.6 watts at 30 Vdc with EOL resistor
installed.
EOL resistor must be ceramic, wirewound type, rated
5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
For HART model, refer to Addendum number 95-8638.
POWER UP TIME—
Fault indication clears after 0.5 second; device is ready
to indicate an alarm condition after 30 seconds.
OUTPUT RELAYS—
Fire Alarm relay, Form C, 5 amperes at 30 Vdc:
The Fire Alarm relay has redundant terminals
and normally open / normally closed contacts,
normally de-energized operation, and latching or
non-latching operation.
Fault relay, Form A, 5 amperes at 30 Vdc:
The Fault relay has redundant terminals and
normally open contacts, normally energized
operation, and latching or non-latching operation.
Auxiliary relay, Form C, 5 amperes at 30 Vdc:
The auxiliary relay has normally open / normally
closed contacts, normally energized or de-energized
operation, and latching or non-latching operation.
CURRENT OUTPUT (Optional)—
0 to 20 milliampere (±0.3 mA) dc current, with a
maximum loop resistance of 500 ohms from 18 to
19.9 Vdc and 600 ohms from 20 to 30 Vdc.
LON OUTPUT—
Digital communication, transformer isolated (78.5 kbps).
TEMPERATURE RANGE—
Operating:
–40°F to +167°F (–40°C to +75°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
Hazardous location ratings from –55°C to +75°C available
on flameproof model.
HUMIDITY RANGE—
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.