F5: Digital Output Option - YASKAWA GA800 Series Technical Reference

Ac drive for industrial applications
Hide thumbs Also See for GA800 Series:
Table of Contents

Advertisement

F4-07: Terminal V1 Signal Level
No.
Name
(Hex.)
F4-07
Terminal V1 Signal Level
(0397)
0 : 0 to 10 V
1 : -10 to 10 V
F4-08: Terminal V2 Signal Level
No.
Name
(Hex.)
F4-08
Terminal V2 Signal Level
(0398)
0 : 0 to 10 V
1 : -10 to 10 V

F5: Digital Output Option

F5 parameters set the output mode and function of output signals when you use digital output option card DO-A3.
When you install a DO-A3 to the drive, you can output isolated digital signals to monitor the drive operation status.
• 6 points of photocoupler output (48 V, 50 mA or less)
• 2 points of relay contact output (250 Vac, 30 Vdc: 1 A or less)
Refer to the DO-A3 option manual for more information about how to install, wire, and set the DO-A3 card.
Use Parameters to Select Output Modes
Use parameter F5-09 [DO-A3 Output Mode Selection] to set signal output from the DO-A3 card.
DO-A3 Terminal Block
TB1
M1-M2
M3-M4
TB2
P1-PC
P2-PC
P3-PC
P4-PC
P5-PC
P6-PC
Coded Output (Binary)
Description
0
No fault
1
oC [Overcurrent], GF
[Ground Fault]
2
ov [Overvoltage]
3
oL2 [Drive Overloaded]
YASKAWA SIEPC71061737B GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
Sets the output signal level for terminal V1.
V/f
CL-V/f
OLV
CLV
Sets the output signal level for terminal V2.
Table 12.45 Details of F5-09 and the DO-A3 Terminal Output
F5-09 = 0 [Predefined
DO-A3 Terminal Name
Individual Outputs] (Default)
Zero speed detection in progress
During speed agreement
oC [Overcurrent], GF [Ground
Fault]
ov [Overvoltage]
oL2 [Drive Overload] or oH2
[Heatsink Overheat]
Not used
oS [Overspeed]
oH, oH1 [Heatsink Overheat] or
oL1 [Motor Overload]
Table 12.46 Binary Output [F5-09 = 1]
Terminal P1-PC
0
1
0
1
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
F5-09 = 1 [Binary Output]
During run
Minor fault (excluding bb
[Baseblock])
Coded output
Note:
Refer to
Table 12.46
details.
Zero speed detection in progress
During speed agreement
DO-A3 Terminal Block TB2
Terminal P2-PC
0
0
1
1
12.7 F: Options
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
F5-09 = 2 [Programmable (F5-
01 to F5-08)]
Depending on the setting of F5-07
[Terminal M1-M2 Function Select]
Depending on the setting of F5-08
[Terminal M3-M4 Function Select]
Depending on the setting of F5-01
[Terminal P1-PC Function Select]
for
Depending on the setting of F5-02
[Terminal P2-PC Function Select]
Depending on the setting of F5-03
[Terminal P3-PC Function Select]
Depending on the setting of F5-04
[Terminal P4-PC Function Select]
Depending on the setting of F5-05
[Terminal P5-PC Function Select]
Depending on the setting of F5-06
[Terminal P6-PC Function Select]
Terminal P3-PC
Terminal P4-PC
0
0
0
0
0
0
0
0
12
797

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents