12.12 T: Auto-Tuning
If the load inertia is too large and the drive detects a fault after Inertia Tuning, decrease the setting. If the drive detects
a fault when T3-01 [Test Signal Frequency] is set to a low value, adjust this parameter.
T3-03: Motor Inertia
No.
Name
(Hex.)
T3-03
Motor Inertia
(0762)
The default setting is for a Yaskawa standard motor as shown in the motor inertia table. Actual values will be different
when you use induction motors or PM motors.
Note:
The display units for the default setting and setting range are different for different models:
• 0.0001 kgm
2
units (setting range: 0.0001 kgm
• 0.001 kgm
2
units (setting range: 0.001 kgm
• 0.01 kgm
2
units (setting range: 0.01 kgm
T3-04: System Response Frequency
No.
Name
(Hex.)
T3-04
System Response Frequency
(0763)
If this input value is too high, it can cause oscillation.

T4: EZ Tuning

Use T4 parameters to input the data necessary for motor parameter Auto-Tuning when A1-02 = 8 [Control Method
Selection = EZ Vector Control]. These two modes are available:
T4-01 Setting
0
Follow the instructions in the setup wizard on the keypad to
manually enter the necessary motor parameters.
1
Do only line-to-line resistance tuning.
*1
When you use a PM motor or a synchronous reluctance motor, it is not necessary to enter the rated frequency. The drive will use the rated
rotation speed and number of motor poles to automatically calculate the rated frequency.
T4-01: EZ Tuning Mode Selection
No.
Name
(Hex.)
T4-01
EZ Tuning Mode Selection
(3130)
0 : Motor Parameter Setting
1 : Line-to-Line Resistance
1004
V/f
CL-V/f
OLV
CLV
Sets the inertia of the motor. This value uses the test signal response to calculate the load inertia.
2
to 6.0000 kgm
2
to 60.000 kgm
2
to 600.00 kgm
2
): 2257 to 2415, 4140 to 4720
V/f
CL-V/f
OLV
CLV
This parameter uses the load inertia value from the Inertia Tuning process to automatically calculate
and set C5-01 [ASR Proportional Gain 1].
Operational overview
V/f
CL-V/f
OLV
CLV
Sets the type of Auto-Tuning for EZOLV control.
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
2
): 2004 to 2021, 4002 to 4012
2
): 2030 to 2211, 4018 to 4103
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Items input for tuning
• T4-02 [Motor Type Selection]
• T4-03 [Motor Max Revolutions]
• T4-04 [Motor Rated Revolutions]
• T4-05 [Motor Rated Frequency]
• T4-06 [Motor Rated Voltage]
• T4-07 [Motor Rated Current]
• T4-08 [Motor Rated Capacity]
• T4-09 [Number of Poles]
Motor Rated Current
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737B GA800 Drive Technical Reference
Determined by o2-04, C6-
01, and E5-01
(0.0001 - 600.00 kgm
(0.1 - 50.0 Hz)
Items tuned
• E9-01 [Motor Type Selection]
• E9-02 [Maximum Speed]
• E9-03 [Rated Speed]
*1
• E9-04 [Base Frequency]
• E9-05 [Base Voltage]
• E9-06 [Motor Rated Current (FLA)]
• E9-07 [Motor Rated Power]
• E9-08 [Motor Pole Count]
• E9-09 [Motor Rated Slip]
• E9-10 [Motor Line-to-Line Resistance]
E9-10 [Motor Line-to-Line Resistance]
Default
(Range)
2
)
Default
(Range)
10.0 Hz
Default
(Range)
0
(0, 1)