“E1” High Pressure Sensor Error; “C4” Odu Jumper Cap Error - Haier GE APPLIANCES Connect Series Service Manual

Split heat pumps
Table of Contents

Advertisement

Troubleshooting
"e1" High Pressure Sensor Error
Error display:
ODU main board LED display
Error judgment condition and method:
Sample the AD value of pressure sensor through
pressure sensor detecting circuit and judge the range of
AD value, If the sampling AD value exceeds upper limit
and lower limit in 30 seconds continuously, report the
error.
Possible causes:
• Poor contact between pressure sensor and terminal in
main board interface
• Pressure sensor is abnormal
• Detecting circuit is abnormal
"C4" ODU Jumper Cap Error
Error display:
ODU main board LED display
Error judgment condition and method:
If jumper cap model doesn't match with main board,
report the error
Possible causes:
• Jumper cap is not installed
• Jumper cap model is wrong
• Detecting circuit is abnormal
Inspect if the
detecting circuit
Replace the main
CONNECT SERIES SERVICE MANUAL
Start
High pressure sensor error
Check if the high pressure sensor
on main board is inserted on the
socket correctly
Yes
Measure the pressure
sensor if its AD value
is normal
No
Yes
Replace the
Replace the
outdoor main
high pressure
board
Start
C4 ODU jumper cap error
Find out JUMP printing on the
main board to see if the jumper
cap is installed at this place
Yes
Check if the jumper
model is correct
No
Yes
Replace the
jumper cap with
is abnormal
correct model
Yes
control board
No
Correctly insert
the pressure
sensor on the
socket
sensor
No
Install the
jumper cap
35