Page 74
9. Air flow and static pressure curves AD072MLERA air flow and static pressure curves super high high static pressure (Pa) AD092MLERA air flow and static pressure curves super high high static pressure (Pa)
Page 75
AD122MLERA air flow and static pressure curves super high high static pressure (Pa) AD162MLERA air flow and static pressure curves 1000 super high high static pressure (Pa)
Page 76
AD182MLERA air flow and static pressure curves 1400 1350 1300 super high 1250 high 1200 1150 1100 1050 1000 static pressure (Pa) AD242MLERA air flow and static pressure curves 1400 1350 1300 super high 1250 high 1200 1150 1100 1050 1000 static pressure (Pa)
Page 77
AD182MMERA air flow and static pressure curves 1400 1300 1200 super high high 1100 1000 static pressure(Pa) AD242MMERA air flow and static pressure curves 1400 1300 1200 super high high 1100 1000 static pressure(Pa)
Page 78
AD282MMERA air flow and static pressure curves 1700 1600 1500 super high high 1400 1300 1200 1100 static pressure(Pa) AD302MMERA air flow and static pressure curves 2300 2200 2100 super high high 2000 1900 1800 1700 static pressure(Pa)
Page 79
AD382MMERA air flow and static pressure curves 2300 2200 2100 super high high 2000 1900 1800 1700 static pressure(Pa) AD482MMERA air flow and static pressure curves 2300 2200 2100 super high high 2000 1900 1800 1700 static pressure(Pa)
Page 80
AD182MHERA air flow and static pressure curves 1400 1200 1000 super high high static pressure (Pa) AD242MHERA air flow and static pressure curves 1400 1200 1000 super high high static pressure (Pa)
Page 81
AD282MHERA air flow and static pressure curves 1400 1200 1000 super high high static pressure (Pa) AD302MHERA air flow and static pressure curves 2000 1800 1600 super high high 1400 1200 1000 static pressure (Pa)
Page 82
AD382MHERA air flow and static pressure curves 2000 1800 1600 super high high 1400 1200 1000 static pressure (Pa) AD482MHERA air flow and static pressure curves 2500 2300 2100 super high high 1900 1700 1500 1300 static pressure (Pa)
Page 83
AD722MHERA, AD962MHERA: 1. The number in the circle stands for the step on the fan speed controller. 2. The red line shows the air flow and the static pressure varies due to the different steps in high speed. The blue dashed line shows the air flow and the static pressure varies due to the different steps in low speed.
Page 84
. Capacity calculation due to capacity modification coefficient...
Page 85
AV10NMVERA AV08NMVERA liquid pipe :φ12.7 liquid pipe :φ12.7 gas pipe :φ22.22 gas pipe :φ22.22 1.00 1.00 0.95 0.95 0.90 0.90 liquid pipe :φ9.52 liquid pipe :φ9.52 gas pipe :φ19.05 gas pipe :φ22.22 0.85 0.85 0.80 0.80 pipe length of single way ( m )
Page 86
AV34NMVERA AV32NMVERA 1.00 1.00 liquid pipe :φ19.05 gas pipe :φ38.1 0.95 0.95 0.90 0.90 liquid pipe :φ19.05 0.85 liquid pipe :φ19.05 0.85 liquid pipe :φ19.05 gas pipe :φ31.8 gas pipe :φ31.8 gas pipe :φ38.1 0.80 0.80 pipe length of single way ( m ) pipe length of single way ( m ) AV36NMVERA AV38NMVERA...
Page 87
(2) Calculation method of heating capacity---Heating capacity to be known = Heating capacityx (A x B x C x D x E x F) W B. Capacity modification value under outdoor air wet-bulb C. Capacity modification value A. Capacity modification value temperature condition under airflow variation rate of under indoor air dry-bulb...
Page 94
a. Allowable pipe length and height difference Single way total pipe length 300m Single way max. pipe length Max. 150m Main pipe between outdoor to 1 branch Max. 90m Pipe length between outdoors Less than 10m to 1 branch pipe Height difference between indoor and Outdoor is upper Max.
Page 95
outdoor1 outdoor 2 outdoor 3 outdoor1 outdoor3 outdoor2 Installation at high difference: outdoor1 outdoor2 outdoor3...
Page 96
outdoor3 outdoor2 outdoor1 Oil trap (upright projecting pipe, 200mm high), as the figure: outdoor2 outdoor3 outdoor1 Below is forbidden (compressor oil will flow into the lowest outdoor). outdoor3 outdoor2 outdoor1...
Page 97
c. Allowable pipe length and height difference outdoor1 when the distance between outdoors is over 2m, the oil trap must be set (upright projecting pipe, 200mm high) outdoor2 outdoor3 below 2m below 2m over 200mm over 200mm L1 < 10m L2+L3 <...
Page 98
(2) Pipe specification: outdoor gather pipe the first branch a. Pipe “a” diameter (between indoor and branch pipe) (depends on indoor pipe, for wall mounted unit, please refer to its specification) Indoor(×100W) Gas pipe Liquid pipe 22~28 φ9.52 φ6.35 36~56 φ12.7 φ6.35 71~140...
Page 100
(1) Outdoor pipe dimension 18~32HP 34~48HP Liquid pipe Liquid pipe Gas pipe Gas pipe The pipe “a, b, c, d” should be confirmed as to the below table. Former outdoor capacity Liquid pipe (a, c) Gas pipe (b, d) ~68.0KW φ15.88 φ28.58 69.0KW~96.0KW...
Page 112
PC on client side install network side software internet or intranet or LAN PC on field (server installed network side software) switch internet server LonWorks pulse ammeter gateway(iGU01) switch...
Page 113
To pulse ammeter To other gateway and server PCB of master unit CN44 CN19 CN36 communication To CN44 of slave unit 1 when there is no Q X Y A B C terminal block when there is no proper power 5V signal from supply from pulse ammeter,...
Page 114
To server bus line 17, 18 connect with server bus line (LON);19 Connect with computer connect with shield layer. earth N L wire...