ADF Web HD67029M-232-20 User Manual

ADF Web HD67029M-232-20 User Manual

M-bus master / modbus slave - converter

Advertisement

Industrial Electronic Devices
User Manual
Revision 3.000
English
M-Bus Master / Modbus Slave -
Converter
(Order Code: HD67029M-232-20, HD67029-B2-232-40,
HD67029-B2-232-80, HD67029-B2-232-160, HD67029-B2-232-250,
HD67029M-485-20, HD67029-B2-485-40, HD67029-B2-485-80,
HD67029-B2-485-160, HD67029-B2-485-250)
For Website information:
www.adfweb.com?Product=HD67029
For Price information:
www.adfweb.com?Price=HD67029M-232-20
www.adfweb.com?Price=HD67029-B2-232-40
www.adfweb.com?Price=HD67029-B2-232-80
www.adfweb.com?Price=HD67029-B2-232-160
www.adfweb.com?Price=HD67029-B2-232-250
www.adfweb.com?Price=HD67029M-485-20
www.adfweb.com?Price=HD67029-B2-485-40
www.adfweb.com?Price=HD67029-B2-485-80
www.adfweb.com?Price=HD67029-B2-485-160
www.adfweb.com?Price=HD67029-B2-485-250
Benefits and Main Features:
Very easy to configure
Electrical isolation
Temperature range: -40°C/85°C (-40°F/185°F)
ADFweb.com S.r.l.
User Manual M-Bus master / Modbus slave - Converter
Document code: MN67029_ENG
For others M-Bus products see also the following link:
Converter M-Bus Wireless to
www.adfweb.com?Product=HD67083
Slave)
www.adfweb.com?Product=HD67084
Converter M-Bus to
www.adfweb.com?Product=HD67021
www.adfweb.com?Product=HD67022
Analyzer / Scanner /Sniffer M-Bus
www.adfweb.com?Product=HD67031
Isolator/Repeater M-Bus
www.adfweb.com?Product=HD67032M
Gateway M-Bus / Modbus TCP
www.adfweb.com?Product=HD67044
Gateway M-Bus / PROFIBUS
www.adfweb.com?Product=HD67053M
Gateway M-Bus Concentrator
www.adfweb.com?Product=HD67054M
Gateway M-Bus Slave / Modbus RTU master
www.adfweb.com?Product=HD67059M-232
Do you have an your customer protocol?
www.adfweb.com?Product=HD67003
Do you need to choose a device? do you want help?
www.adfweb.com?Cmd=helpme
User Manual
Revision 3.000
Page 1 of 47
(Modbus TCP
(Ethernet)
(RS232)
(RS485)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HD67029M-232-20 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ADF Web HD67029M-232-20

  • Page 1 Industrial Electronic Devices User Manual Revision 3.000 English M-Bus Master / Modbus Slave - Converter (Order Code: HD67029M-232-20, HD67029-B2-232-40, HD67029-B2-232-80, HD67029-B2-232-160, HD67029-B2-232-250, HD67029M-485-20, HD67029-B2-485-40, HD67029-B2-485-80, HD67029-B2-485-160, HD67029-B2-485-250) For others M-Bus products see also the following link: For Website information: Converter M-Bus Wireless to www.adfweb.com?Product=HD67029...
  • Page 2: Table Of Contents

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 2 of 47 Industrial Electronic Devices INDEX: UPDATED DOCUMENTATION: Dear customer, we thank you for your attention and we remind you that Page you need to check that the following document is: INDEX UPDATED DOCUMENTATION Updated...
  • Page 3: Security Alert

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 3 of 47 Industrial Electronic Devices SECURITY ALERT: ENERAL NFORMATION To ensure safe operation, the device must be operated according to the instructions in the manual. When using the device, legal and safety regulation are required for each individual application.
  • Page 4: Example Of Connection

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 4 of 47 Industrial Electronic Devices EXAMPLE OF CONNECTION: ADFweb.com S.r.l.
  • Page 5: Connection Scheme

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 5 of 47 Industrial Electronic Devices CONNECTION SCHEME: Figure 1a: Connection scheme for HD67029M-232-20 ADFweb.com S.r.l.
  • Page 6 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 6 of 47 Industrial Electronic Devices Figure 1b: Connection scheme for HD67029M-485-20 ADFweb.com S.r.l.
  • Page 7 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 7 of 47 Industrial Electronic Devices Figure 1c: Connection scheme for HD67029-B2-232-xxx ADFweb.com S.r.l.
  • Page 8 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 8 of 47 Industrial Electronic Devices Figure 1c: Connection scheme for HD67029-B2-485-xxx ADFweb.com S.r.l.
  • Page 9: Characteristics

    At the Converter can be connected up to 250 standard M-Bus devices. This number depends of the code expressed by the xxx number: HD67029M-232-20 or HD67029M-485-20 support up to 20 M-Bus devices; HD67029-B2-232-40 or HD67029-B2-485-40 support up to 40 M-Bus devices;...
  • Page 10: Power Supply

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 10 of 47 Industrial Electronic Devices POWER SUPPLY: The devices can be powered at 15…21V AC and 18…35V DC. The consumption depends to the code of the device. For more details see the two tables below.
  • Page 11: Function Modes

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 11 of 47 Industrial Electronic Devices FUNCTION MODES: The device has got two functions mode depending of the position of the Dip2 of ‘Dip-Switch A’ of HD67029M-xxx-20 or Dip1 of ‘Dip-Switch A’ of HD67029-B2-xxx-xxx: The first, with Dip2 of ‘Dip-Switch A’...
  • Page 12: Leds

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 12 of 47 Industrial Electronic Devices LEDS: HD67029M- -20: The HD67029M-xxx-20 device has got four LEDs that are used to give information of the functioning status. The various meanings of the LEDs are described in the table below.
  • Page 13 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 13 of 47 Industrial Electronic Devices HD67029-B2- The device has got five LEDs that are used to give information of the functioning status. The various meanings of the LEDs are described in the table below. Normal Mode Boot Mode Blinks quickly: Boot state...
  • Page 14: Rs232

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 14 of 47 Industrial Electronic Devices RS232: The connection from RS232 socket to a serial port (example one from a personal computer) must be made with a Null Modem cable (a serial cable where the pins 2 and 3 are crossed).
  • Page 15: Rs485

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 15 of 47 Industrial Electronic Devices RS485: To terminate the RS485 line with a 120Ω resistor, it is necessary to put dip 1 ON, like in figure. The maximum length of the cable should be 1200m (4000 feet).
  • Page 16: M-Bus

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 16 of 47 Industrial Electronic Devices M-BUS: The M-Bus is a unpolarized bus. A two wire standard telephone cable (JYStY N*2*0.8 mm) is used as the transmission medium for the M- Bus.
  • Page 17: Use Of Compositor Sw67029

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 17 of 47 Industrial Electronic Devices USE OF COMPOSITOR SW67029: To configure the Converter, use the available software that runs with Windows called SW67029. It is downloadable from the site www.adfweb.com and its operation is described in this document (this manual is referenced to the last version of the software present on the web site).
  • Page 18: New Configuration / Open Configuration

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 18 of 47 Industrial Electronic Devices NEW CONFIGURATION / OPEN CONFIGURATION: “New Configuration” button creates the folder which contains the entire device’s configuration. A device’s configuration can also be imported or exported: To clone the configurations of a programmable “M-Bus master / Modbus slave - Converter”...
  • Page 19: Software Options

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 19 of 47 Industrial Electronic Devices SOFTWARE OPTIONS: By pressing the “Settings” ( ) button there is the possibility to change the language of the software and check the updatings for the compositor.
  • Page 20: Set Communication

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 20 of 47 Industrial Electronic Devices SET COMMUNICATION: This section define the fundamental communication parameters of two buses, Modbus and M-Bus. By Pressing the “Set Communication”...
  • Page 21 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 21 of 47 Industrial Electronic Devices The means of the fields for “M-Bus” are: In the field “Baudrate” the data rate of the M-Bus net is defined; In the field “Parity”...
  • Page 22: M-Bus

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 22 of 47 Industrial Electronic Devices M-BUS By Pressing the “M-Bus” button from the main window for SW67029 (Fig. 2) the window “M-Bus Network” appears (Fig. 4). In the section “Nodes”...
  • Page 23 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 23 of 47 Industrial Electronic Devices If the field “Send SND_NKE” is checked, the Converter send the “SND_NKE” frame to start the communication. In the field “Send Reset App.”...
  • Page 24 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 24 of 47 Industrial Electronic Devices ECTION ARIABLES Selecting the desired node it is possible to add a variable. In order to create a new variable it is necessary to fill these items: To use the created variable the field “Enable Variable”...
  • Page 25 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 25 of 47 Industrial Electronic Devices In the field “Tariff” if it is necessary it is possible to insert the value of the tariff of that variable. The Tariff is used for indicates from which device the data come;...
  • Page 26 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 26 of 47 Industrial Electronic Devices SECTION VARIABLES (BY POSITION): Selecting the desired node it is possible to add a variable. In order to create a new variable it is necessary to fill these items: To use the created variable the field “Enable Variable”...
  • Page 27 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 27 of 47 Industrial Electronic Devices If the field “Force Integer 32” is checked the Converter maps the variables with a dimension <32 bit in two consecutive Modbus registers as a 32 bit variables;...
  • Page 28 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 28 of 47 Industrial Electronic Devices Example: 0x68 - Start Byte 0xBD - L Fied 0xBD - L Field 0x68 - Start Byte 0x08 - C Field 0x02 - A Field 0x72 - CI Field Identification Number (or Secondary Address) put in the...
  • Page 29 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 29 of 47 Industrial Electronic Devices ASTE AND ELETE TEMS By pressing the right button of the mouse over an item (Variable or Node) it is possible to Copy, Paste and Delete. It is possible to Copy a variable from a Node and copy it to another Node, or copy a Variable from a project and paste in another one.
  • Page 30 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 30 of 47 Industrial Electronic Devices Possible choices for the fields used to create a variable: Type of Data: Function Field: |_Energy (Wh) |_Instantaneous Value |_Energy (J) |_Minimum Value |_Volume (m...
  • Page 31 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 31 of 47 Industrial Electronic Devices VIFE: |_ Not Selected |_ Period of tariff months(s) |_ Credit of the nominal local legal currency units |_ Period of tariff year(s) |_ Debit of the nominal local legal currency units |_ dimensionless/ no VIF |_ Access Number (transmission count)
  • Page 32 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 32 of 47 Industrial Electronic Devices |_ per second |_ Duration of limit exceed |_ per minute |_ Duration of first/last |_ per hour |_ Date(/time) of first/last begin/end |_ per day |_ Multiplicative currection factor |_ per week...
  • Page 33 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 33 of 47 Industrial Electronic Devices Swap Identification: This field is used for select the Swap mode of Identification Number. At the moment there are these possibilities: None;...
  • Page 34 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 34 of 47 Industrial Electronic Devices To know the meaning of value read in the “Modbus Re Scale” field, you must follow this table (x = Value read in Modbus Re Scale): Description Range Coding Range...
  • Page 35 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 35 of 47 Industrial Electronic Devices Data type F: Min (0 … 59); Hour (0 … 23); Day (1 … 31); Month (1 … 12); Year (0 …...
  • Page 36: Manufacturer Specific Data

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 36 of 47 Industrial Electronic Devices MANUFACTURER SPECIFIC DATA Using this function is possible to save into Modbus registers the part of M-Bus frame that is coded like Manufacturer Specific Data. Usually these data are at the end of the frame and after a DIF byte with the value 0x0F of 0x1F.
  • Page 37: Update Device

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 37 of 47 Industrial Electronic Devices UPDATE DEVICE (FOR HD67029M): By pressing the “Update Device” button it is possible to load the created Configuration into the device, and also the Firmware if is necessary, using the RS232 port.
  • Page 38 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 38 of 47 Industrial Electronic Devices UPDATE DEVICE (FOR HD67029-B2): By pressing the “Update Device” button, it is possible to load the created Configuration into the device;...
  • Page 39 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 39 of 47 Industrial Electronic Devices Note: When you receive the device, for the first time, you also have to update the Firmware in the HD67029 device. Warning: If Fig.
  • Page 40: Scan & Decode

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 40 of 47 Industrial Electronic Devices SCAN & DECODE FUNCTION: “SCAN & DECODE” functions are integrated in the configurator software SW67029. It is possible to access to these functions by simple click on the “...
  • Page 41: Mechanical Dimensions

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 41 of 47 Industrial Electronic Devices MECHANICAL DIMENSIONS: Figure 7a: Mechanical dimensions scheme for HD67029M-xxx-20 ADFweb.com S.r.l.
  • Page 42 User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 42 of 47 Industrial Electronic Devices Figure 7b: Mechanical dimensions scheme for HD67029-B2-xxx-xxx ADFweb.com S.r.l.
  • Page 43: Ordering Informations

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 43 of 47 Industrial Electronic Devices ORDERING INFORMATIONS: The ordering part number is formed by a valid combination of the following: HD67029 M – xxx - 20 Maximum number of slaves supported 20: up to 20 standard slaves (1.5mA consumption) connected to M-Bus Serial port...
  • Page 44 B: Modulbox 4M DIN Rail mounting Device Family HD67029: M-Bus / Modbus – Converter Order Code: HD67029M-232-20 - M-Bus master / Modbus slave (RS232) - Converter (up to 20 slaves connected to M-Bus) Order Code: HD67029-B2-232-40 - M-Bus master / Modbus slave (RS232) - Converter (up to 40 slaves connected to M-Bus)
  • Page 45: Accessories

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 45 of 47 Industrial Electronic Devices ACCESSORIES: Order Code: APW020 Power Supply for M-Bus Master device that supports up to 20 Slaves Order Code: APW040 Power Supply for M-Bus Master device that supports up to 40 Slaves Order Code: APW080...
  • Page 46: Disclaimer

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 46 of 47 Industrial Electronic Devices DISCLAIMER: All technical content within this document can be modified without notice. The content of the document is a under continual renewal. For losses due to fire, earthquake, third party access or other accidents, or intentional or accidental abuse, misuse, or use under abnormal conditions repairs are charged to the user.
  • Page 47: Warranties And Technical Support

    User Manual M-Bus master / Modbus slave - Converter Document code: MN67029_ENG Revision 3.000 Page 47 of 47 Industrial Electronic Devices WARRANTIES AND TECHNICAL SUPPORT: For fast and easy technical support for your ADFweb.com SRL products, consult our internet support at www.adfweb.com. Otherwise contact us at the address support@adfweb.com RETURN POLICY: If while using your product you have any problem and you wish to exchange or repair it, please do the following:...

Table of Contents