Volume Flow In Dependence Of The Heat Power Dissipation And Temperature Difference; Figure 29: Volume Flow In Dependence Of The Heat Power Dissipation And Temperature Difference - KEB COMBIVERT F5 Series Instructions For Use Manual

Installation active infeed controller
Hide thumbs Also See for COMBIVERT F5 Series:
Table of Contents

Advertisement

COOLING SySTEM
NOTICE
10.1.5.3 Volume flow in dependence of the heat power dissipation and temperature difference
ΔT in K
12
11
10
9
8
7
6
5
4
3
2
1
0
2
3
4
Legend
Master / Slave / Slave 9...12 ΔT in K
Master / Slave 6...10 ΔT in K
Master 3...6 ΔT in K
10 l/min
Figure 29:

Volume flow in dependence of the heat power dissipation and temperature difference

68
The maximum temperature difference between pre-run and return flow
is specified in the technical data and should not be exceeded. If the vol-
ume flow (above 30 l/min per module) is selected too large, increases
the risk of erosion in the liquid cooler.
5
6
7
8
9
10
11
12
15 l/min
20 l/min
25 l/min
30 l/min
13
14
15
Pv in kW