COOLING SySTEM
10.1.5.1 Pressure drop of the heat sink depending on the flow rate
The pump capacity required for the COMBIVERT F5 is derived from the following spec-
ifications, which are represented in the diagram chapter „Connection scheme for a cool-
ing circuit (series connection)".
bar
4,0
3,6
3,2
2,8
2,4
2,0
1,6
1,2
0,8
0,4
0,0
4
6
8
10
Legend
Recommended working range 10...30 in l/min
Single device
Series connection of two modules (Master/Slave)
Series connection of three modules (Master/Slave/Slave)
Figure 27:

Pressure drop of the heat sink depending on the flow rate

66
12
14
16
18
20
The choice of the connection scheme (series or parallel connection) of the
coolant circuit is dependent on the heat power dissipation and the selected
switching frequency of the drive converter system.