Technical Specifications - baltur TBG 85 MC Instruction Manual For Installation, Use And Maintenance

Modulating two-stage gas burners
Table of Contents

Advertisement

Available languages

Available languages

TECHNICAL SPECIFICATIONS

MODEL
Type-approval PIN
Maximum natural gas heat power
Minimum natural gas heat power
¹) natural gas emissions
Operation
50 Hz natural gas transformer
60 Hz natural gas transformer
Maximum natural gas heat rate
Minimum natural gas heat rate
Maximum natural gas pressure
Minimum natural gas pressure
Maximum propane thermal power
Minimum propane thermal power
Maximum propane thermal flow rate
Minimum propane thermal flow rate
Maximum propane pressure
Minimum propane pressure
²)propane emissions
50hz fan motor
60hz fan motor
Absorbed electrical power* 50hz
Absorbed electrical power* 60hz
50 Hz power supply voltage
60 Hz power supply voltage
Protection rating
Flame detection
Control box
Air flow rate regulation
Operating ambient air temperature
Sound pressure**
Weight with packaging
Weight without packaging
Calorific power below reference conditions 15° C, 1013 hPa (mbar):
Natural gas: Hi = 9,45 kWh/Stm³ = 34,02 MJ/Stm³
Propane: Hi = 24,44 kWh/Stm³ = 88,00 MJ/Stm³
For different types of gases and pressure values, contact our sales departments.
* Total absorption at start-up with ignition transformer on.
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory environment
conditions and cannot be compared to measurements carried out in different locations.
Propane / natural gas CO emissions ≤ 100 mg/kWh
¹) NATURAL GAS EMISSIONS
Classes defined according to EN 676 standards.
Class
NOx emissions in mg/kWh natural gas
1
2
3
kW
kW
mg/kWh
Two-stage progressive /
26 kV 40 mA - 230 V
26 kV 40 mA - 230 V
Stm³/h
Stm³/h
hPa (mbar)
hPa (mbar)
kW
kW
Stm³/h
Stm³/h
hPa (mbar)
hPa (mbar)
mg/kWh
kW
kW
kW
kW
IONISATION PROBE
MECHANICAL CAM
°C
dBA
kg
kg
≤ 170
≤ 120
≤ 80
5 / 34
0006160008_201912
TBG 85 MC
TBG 120 MC
CE-0085BS0067
CE-0085BS0067
850
170
Class 2
Class 2
Two-stage progressive /
modulating
modulating
26 kV 40 mA - 230 V
26 kV 40 mA - 230 V
90
18
360
31
850
170
34.7
6.9
360
31
Class 2
Class 2
1.1
1.1
1.6
1.6
3N~ 400V ± 10%
3N~ 400V ± 10%
3N~ 380V ± 10%
3N~ 380V ± 10%
IP54
IONISATION PROBE
LME 22...
LME 22...
MECHANICAL CAM
-15 ÷ +40
-15 ÷ +40
73
77.53
67
²) PROPANE GAS EMISSIONS
Classes defined according to EN 676 standards.
Class
NOx emissions in mg/kWh propane gas
1
2
3
TBG 150 MC
CE-0085BS0067
1200
1500
240
300
Class 2
Two-stage progressive /
modulating
26 kV 40 mA - 230 V
26 kV 40 mA - 230 V
127
158.7
25.4
31.8
360
360
20
21.7
1200
1500
240
300
49
61.3
9.8
12.3
360
360
30
46
Class 2
1.5
2.2
1.5
2.6
2
2.8
2
3.2
3N~ 400V ± 10%
3N~ 380V ± 10%
IP54
IP54
IONISATION PROBE
LME 22...
MECHANICAL CAM
-15 ÷ +40
75.5
79
85
92
67
71
≤ 230
≤ 180
≤ 140
ENGLISH

Hide quick links:

Advertisement

Chapters

Table of Contents
loading