Post-Connection Check - Endress+Hauser Liquiphant FTL51B Operating Instructions Manual

Vibronic limit switch for liquids
Hide thumbs Also See for Liquiphant FTL51B:
Table of Contents

Advertisement

Liquiphant FTL51B
Endress+Hauser
3.5
2
1
 35
Cable entry, electronic insert
1
M20 cable gland
2
Conductor cross-section, 2.5 mm
3
Conductor cross-section, 4.0 mm
ød
Nickel-plated brass 7 to 10.5 mm (0.28 to 0.41 in)
ød
Plastic 5 to 10 mm (0.2 to 0.38 in)
ød
Stainless steel 7 to 12 mm (0.28 to 0.47 in)
Secure the cable gland and tighten the union nut of the cable gland, 8 Nm (5.9 lbf ft)
torque. Screw the enclosed cable glands into the housing with a torque of
3.75 Nm (2.76 lbf ft).
6.3

Post-connection check

 Is the device or cable undamaged (visual inspection)?
 Do the cables used comply with the requirements?
 Do the mounted cables have adequate strain relief?
 Are the cable glands mounted and firmly tightened?
 Does the supply voltage match the specifications on the nameplate?
 No reverse polarity, is terminal assignment correct?
If supply voltage is present, is the green LED lit?
 Are all the housing covers installed and tightened?
 Optional: Is the cover with securing screw tightened?
3
2
maximum (AWG14)
2
maximum (AWG12)
Electrical connection
A0018023