5.2.2

Installation

Horizontal installation in vessels
Align the tuning fork with the marking
316L/G1
 14
Marking to align the tuning fork
Use the marking to align the tuning fork in such a way that medium can run off easily and
deposit buildup is avoided.
The following can be used as the marking:
• Material specification, thread description or circle on the hexagonal nut or on the weld-
in adapter
• The II symbol on the back of the flange or Tri-Clamp
Installing in pipes
 15
Marking and fork position
• Flow velocity up to 5 m/s with viscosity 1 mm
Check for correct functioning in the event of other process medium conditions
• The marking on the adapter points in the flow direction; the flow is thus not severely
obstructed
• The marking can be identified while the device is installed
Screwing in the device
 16
Screwing in the device
• Turn by the hex bolt only, 15 to 30 Nm (11 to 22 lbf ft)
• Do not turn at the housing!
2
/s (cSt) and density 1 g/cm