Figure 6-22
Options for the assignment of the terminal block, terminal rows C and D
6.2.6

Spark suppression: Example

NOTICE
Damage to the digital outputs due to missing external protective circuit
Arcs can result when switching inductances without external protective circuit; these can
damage the digital outputs/relays.
• Install an adequate external protective circuit with inductive or ohmic-inductive loading of
• Refer to the following paragraphs as an example.
Quick Start
Compact Operating Instructions, 05/2018, A5E31805656-06
the digital outputs/relays.