Mitsubishi Electric MELSEC iQ-R Series User Manual page 169

Melsecnet/h network module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

No.
Name
SW00AE
Offline test execution item
of responding side
SW00AF
Offline test result of
responding side
SW00B0
Multiplex transmission
to
status of forward loop
SW00B3
side
SW00B4
Multiplex transmission
to
status of reverse loop
SW00B7
side
SW00B8
UNDER on the forward
loop side
SW00B9
CRC on the forward loop
side
SW00BA
OVER on the forward
loop side
Description
Shows the items of the offline test at the response side.
3: Loop test (Forward loop)
4: Loop test (Reverse loop)
(Conditions)
• This register is enabled when 'Offline test response completion (issuance at another
station)' (SB00AF) is on.
Stores the results of the offline test at the response side.
0: Completed normally
1 or greater: Completed with an error (An error code is stored.)
(Conditions)
• This register is enabled when 'Offline test response completion (issuance at another
station)' (SB00AF) is on.
Stores the forward loop (IN-side) use status of each station during multiplex transmission.
Off: Other than forward loop (IN-side)
On: Forward loop (IN-side) used
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW00B0
16 15 14 13 12 11 10
SW00B1
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW00B2
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW00B3
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
Each number in the table represents a station number.
(Conditions)
• This register is enabled when 'Baton pass error status of own station' (SB0047) is off.
When 'Baton pass error status of own station' (SB0047) is turned on (error), data prior
to error is held.
• Reserved stations and stations with a number equal to or greater than the maximum
station number are ignored.
Stores the reverse loop (OUT-side) use status of each station during multiplex
transmission.
Off: Other than reverse loop (OUT-side)
On: Reverse loop (OUT-side) used
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW00B4
16 15 14 13 12 11 10
SW00B5
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW00B6
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW00B7
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
Each number in the table represents a station number.
(Conditions)
• This register is enabled when 'Baton pass error status of own station' (SB0047) is off.
When 'Baton pass error status of own station' (SB0047) is turned on (error), data prior
to error is held.
• Reserved stations and stations with a number equal to or greater than the maximum
station number are ignored.
Stores the cumulative error occurrence count of the forward loop (IN-side) communication
under-error.
0: No error
1 or greater: Cumulative count
There is no problem if values are counted up little by little over a long period of time. If
values are rapidly counted up in a short period of time, check if the cables are faulty.
Stores the cumulative error occurrence count of the forward loop (IN-side) communication
CRC error.
0: No error
1 or greater: Cumulative count
There is no problem if values are counted up little by little over a long period of time. If
values are rapidly counted up in a short period of time, check if the cables are faulty.
Stores the cumulative error occurrence count of the forward loop (IN-side) communication
overrun error.
0: No error
1 or greater: Cumulative count
There is no problem if values are counted up little by little over a long period of time. If
values are rapidly counted up in a short period of time, check if the cables are faulty.
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
Appendix 4 List of Link Special Register (SW) Areas
Availability
Control
Normal
station
Station
A
APPX
167