Setting Check Test

Select "Test Method" and "Target Module" and click the [Execute] button.
The following three checks are performed:
• Checking for the presence of any duplicated control station
• Checking for the presence of any duplicated station number
• Checking for consistency between the network number set for the station connected with the engineering tool and the
network number set in the network parameter of the own station
Item
Network Information
Setting
Test Method
Check Test
Target Module
Execution
1 to 64
Result
Control Station Duplicated
Duplicated Station No.
Network No.
Group No.
Reserved station
Error Station
Network Type Error Station
Multiplexed R Sub M Station
(Multiplexed remote sub-master
station duplication)
Parallel R Sub M Station
(Parallel remote sub-master
station duplication)
Description
Indicates the same information as own station information. ( Page 106 Host Station Information)
■Parameter Specified
Select this item to test the total number of stations set in the network parameters (excluding reserved
stations).
If no network parameter exists, test is performed for all stations.
■All Stations Specified
Select this item to test all stations.
Select a module to perform setting check test.
Indicates the station number of the station for which the setting check test was executed. (Up to 64
stations)
Places the  sign for the control stations whose station number is duplicated.
Places the  sign for the target stations whose station number is duplicated.
Indicates the network number of the station for which the setting check test was executed. The station
whose network number is different from that of the own station is indicated in red.
Indicates the group number of the station for which the setting check test was executed. (When the test
execution method is set to "Parameter Specified")
Places the  sign for stations that are specified as a reserved station by the parameter setting. (When the
test execution method is set to "Parameter Specified")
Places the  sign for any stations that are specified as a reserved station by the parameter setting or
whose module is faulty in all stations specification.
Places the  sign for any stations whose parameter setting and the actual connection type are
inconsistent.
Places the  sign for any submaster stations that are in the same network.
4 TROUBLESHOOTING