Direct access to link devices

This function allows direct access to the link devices of the RJ71LP21-25 from the program.
Specify a link device (LB, LW, LX, LY, SB, SW) as the link direct device (J\) for direct access.
Specification method
Specify the network number and the link device of the RJ71LP21-25 for reading or writing.
J
\
(1) (2)
(1) Network number: 1 to 239
(2) Link device
Link relay (LB): B0 to B3FFF
Link register (LW): W0 to W3FFF
Link input (LX): X0 to X1FFF
Link output (LY): Y0 to Y1FFF
Link special relay (SB): SB0 to SB1FF
Link special register (SW): SW0 to SW1FF
Ex.
Send request
J1\B0
J1\B100
Send request
MOV K20 J1\W100
= J1\W200 K300
Output instruction
J1\Y1000
J1\X1100