No.
Name
SW0044
Station setting
SW0046
Module type
SW0047
Baton pass status of own
station
SW0048
Cause of baton pass
interruption
SW0049
Cause of data link stop
APPX
158
Appendix 4 List of Link Special Register (SW) Areas
Description
Stores the settings status of the own station.
b15
b14
b13 b12 b11 b10
b9
0
0
0
0
0
0
SW0044
b0: Network type
• 0: PLC to PLC network (Fixed to 0)
b1: Station type
• 0: Normal station
• 1: Control station
b7: Control station operation
• 0: Specified control station switching
• 1: Current control station maintained
b8: Operation mode
• 0: Online mode
• 1: Debug mode
b12: Own station network type
• 0: MELSECNET/H mode, MELSECNET/10 mode
• 1: MELSECNET/H extended mode
Stores the hardware status of the own station.
...
b15
b14
b13
b2 b1
...
0
0
0
SW0046
b1 to b0: Hardware status
• 01: Light (fixed at 01)
b14: Hardware status
• 0: Duplex (fixed at 0)
b15: Hardware status
• 0: Loop (fixed at 0)
Stores the baton pass status (transient transmission availability) of the own station.
00H: Data link in progress
01H: Data link stop (Instructed by another station)
02H: Data link stop (Instructed by the own station)
03H: Baton pass in progress (Parameter received (No own station send area))
04H: Baton pass in progress (Parameter error)
05H: Baton pass in progress (Parameter not received)
06H: Disconnecting (No baton pass)
07H: Disconnecting (Line error)
11H: Loop test
12H: Setup check test
13H: Station order check test
14H: Communication test
1FH: Offline test
Stores the cause of interruption in the communication (baton pass) of the own station.
00H: Normal communication
01H: Offline
02H: Offline test
03H or greater: Cause of interruption (Error code)
Stores the cause which stopped the data link of the own station.
00H: Normal
01H: Stop direction
02H: No common parameter exists
03H: Common parameter error
04H: Own station CPU error
06H: Communication interruption
...
b8
b7
b6
b2 b1 b0
...
0
0
b0
Availability
Control
Normal
station
Station