Error code
Error details and causes
*1
FD01H
A CRC error has occurred during the
execution of the station-to-station test
and self-loopback test.
*1
FD02H
An overrun error has occurred during
the execution of the station-to-station
test and self-loopback test.
*1
FD03H
An abort error has occurred during the
execution of the station-to-station test
and self-loopback test.
*1
FD04H
A timeout error has occurred during the
execution of the station-to-station test
and self-loopback test.
*1
FD05H
A data error has occurred during the
execution of the station-to-station test
and self-loopback test.
*1
FD06H
An under-error has occurred during the
execution of the station-to-station test
and self-loopback test.
*1
FD07H
The sending data has failed during the
execution of the station-to-station test
and self-loopback test.
*1
FD08H
The sending data has failed during the
execution of the station-to-station test
and self-loopback test.
FD09H
The loop status is changed during the
execution of the loop test.
FD0AH
The loop status is unstable during the
execution of the loop test.
FD0BH
Wiring error is detected during the
execution of the loop test.
FD0CH
An error was detected in the network
module.
FD11H
The setting check test, station order
check test, loop test, and
communication test are executed in
duplicate.
FD12H
The setting check test, station order
check test, and loop test are executed
during disconnection.
FD13H
An error was detected in the test data.
FD14H
An error was detected in the network
module.
FD15H
Send operation has failed in online test.
FD16H to FD17H
An error was detected in the test data.
FD18H to FD19H
An error was detected in the network
module.
FD1AH
The station whose station number is
duplicated is detected by the station
order check test.
FD1BH
The test is interrupted.
4 TROUBLESHOOTING
136
4.5 List of Error Codes
Action
No action is required because the system performs a retry. However, if the
error occurs frequently, check for cable failure, hardware failure, noise,
and wiring error.
No action is required because the system performs a retry. However, if the
error occurs frequently, check for cable failure, hardware failure, noise,
and wiring error.
No action is required because the system performs a retry. However, if the
error occurs frequently, check for cable failure, hardware failure, noise,
and wiring error.
No action is required because the system performs a retry. However, if the
error occurs frequently, check for cable failure, hardware failure, noise,
and wiring error.
No action is required because the system performs a retry. However, if the
error occurs frequently, check for cable failure, hardware failure, noise,
and wiring error.
No action is required because the system performs a retry. However, if the
error occurs frequently, check for cable failure, hardware failure, noise,
and wiring error.
No action is required because the system performs a retry. However, if the
error occurs frequently, check for cable failure, hardware failure, noise,
and wiring error.
Check for coaxial cable connection and looseness, terminating resistor
connection, and cable failure.
No action is required because the system performs a retry. (Do not switch
the loop in the middle.) However, if the error occurs frequently, check the
line and wiring status.
No action is required because the system performs a retry. (Do not switch
the loop in the middle.) However, if the error occurs frequently, check the
line and wiring status.
Check the wiring.
Please consult your local Mitsubishi representative.
Perform the test after the completion of the test from another station.
Eliminate the cause of disconnection and take actions.
• Check for cable failure, hardware failure, wiring error, station number
duplication, control station duplication, and mismatched transmission
speed in the module in the same network.
• If the error occurs again, please consult your local Mitsubishi
representative.
Please consult your local Mitsubishi representative.
Check for cable failure, hardware failure, noise, and wiring error.
• Check for cable failure, hardware failure, wiring error, station number
duplication, control station duplication, and mismatched transmission
speed in the module in the same network.
• If the error occurs again, please consult your local Mitsubishi
representative.
Please consult your local Mitsubishi representative.
Correct the station whose station number is duplicated.
• Retry the test.
• If the error occurs again, the error is the hardware failure of the network
module. Please consult your local Mitsubishi representative.