Checking The Power Supply; Checking The Binary I/O Circuits; Binary Input Circuits; Binary Output Circuits - ABB Relion 670 Series Installation And Commissioning Manual

Generator protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 502 029-UEN A
6.4
6.5
6.5.1
6.5.2
6.6
Installation and commissioning manual
Checking the external optical and electrical connections

Checking the power supply

Check that the auxiliary supply voltage remains within the permissible input
voltage range under all operating conditions. Check that the polarity is correct
before powering the IED.

Checking the binary I/O circuits

Binary input circuits

Preferably, disconnect the binary input connector from the binary input cards.
Check all connected signals so that both input level and polarity are in accordance
with the IED specifications.

Binary output circuits

Preferably, disconnect the binary output connector from the binary output cards.
Check all connected signals so that both load and polarity are in accordance with
IED specifications.

Checking optical connections

Check that the Tx and Rx optical connections are correct.
An IED equipped with optical connections requires a minimum
depth of 180 mm for plastic fiber cables and 275 mm for glass fiber
cables. Check the allowed minimum bending radius from the
optical cable manufacturer.