ABB Relion 670 Series Installation And Commissioning Manual page 79

Generator protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 502 029-UEN A
Installation and commissioning manual
REX061 Capacitor unit connections
Table 15:
Injection and rotor connection X1
No
1
Rotor positive pole
2
-
3
Positive pole
4
-
5
Negative pole
6
-
7
Rotor negative pole
8
-
9
Rotor injection
10
Injection ground. Internally connected to chassis and PE
Table 16:
Measurment connector X2
No
1
Rotor + voltage divided by 1 000
2
Ground
3
Rotor - voltage divided by 1 000
X1 connector. Connect each signal connector terminal of screw compression type
2
with one 0.14 to 6 mm
X2 connector. Connect each signal connector terminal of screw compression type
2
with one 0.5 to 2.5 mm
Grounding (PE). Protective earth is a separate 4 mm screw terminal.
REX062 Shunt resistor unit connections
Table 17:
Injection via shunt resistors connection X1
No
1
-
2
Injection
3
-
4
Injection return
5
-
6
Current sense output
7
-
8
Current sense output
9
Injection input, External shunt
10
Injection input return, External shunt
Signal
Signal
wire or with two 0.14 to 1.5 mm
wire or with two 0.5 to 1.0 mm
Signal
Section 5
Installing the IED
2
wires.
2
wires.
73