ABB Relion 670 Series Installation And Commissioning Manual page 247

Generator protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 502 029-UEN A
Installation and commissioning manual
Self-supervision summary = INT--FAIL and INT--WARNING
CPU-module status summary = INT--NUMFAIL and INT--NUMWARN
When an internal fault has occurred, extensive information about the fault can be
retrieved from the list of internal events available in the SMS part:
TRM-STAT TermStatus - Internal Events
The list of internal events provides valuable information, which can be used during
commissioning and fault tracing.
The internal events are time tagged with a resolution of 1ms and stored in a list.
The list can store up to 40 events. The list is based on the FIFO principle, when it is
full, the oldest event is overwritten. The list cannot be cleared and its content
cannot be erased.
The internal events in this list not only refer to faults in the IED, but also to other
activities, such as change of settings, clearing of disturbance reports, and loss of
external time synchronization.
The information can only be retrieved from the Parameter Setting software
package. The PC can be connected either to the port at the front or at the rear of the
IED.
These events are logged as internal events.
Table 32:
Events available for the internal event list in the IED
Event message:
INT--FAIL
Off
INT--FAIL
INT--WARNING
Off
INT--WARNING
INT--NUMFAIL
Off
INT--NUMFAIL
INT--NUMWARN
Off
INT--NUMWARN
IOn--Error
Off
IOn--Error
ADMn-Error
Off
ADMn-Error
MIM1-Error
Off
MIM1-Error
INT--RTC
Off
INT--RTC
Table continues on next page
Fault tracing and repair
Description
Internal fail status
Internal warning status
Numerical module fatal error
status
Numerical module non-fatal
error status
In/Out module No. n status
Analog/Digital module No. n
status
mA-input module status
Real Time Clock (RTC) status
Section 18
Generating signal:
INT--FAIL (reset event)
INT--FAIL (set event)
lNT--WARNING (reset event)
lNT--WARNING (set event)
INT--NUMFAIL (reset event)
INT--NUMFAIL (set event)
INT--NUMWARN (reset
event)
INT--NUMWARN (set event)
IOn--Error (reset event)
IOn--Error (set event)
ADMn-Error (reset event)
ADMn-Error (set event)
MIM1-Error (reset event)
MIM1-Error (set event)
INT--RTC (reset event)
INT--RTC (set event)
241