HPE 800W Flex Slot -48VDC Hot-plug Low Halogen Power Supply

Specification
Input requirements
Rated input voltage
Rated input current
Rated input power (W)
Rated input power (BTUs per hour)
Power supply output
Rated steady-state power (W)
Maximum peak power (W)
Maximum peak power
WARNING: To reduce the risk of electric shock or energy hazards:
This equipment must be installed by trained service personnel.
Connect the equipment to a reliably grounded secondary circuit source. A secondary circuit has no direct
connection to a primary circuit and derives its power from a transformer, converter, or equivalent isolation
device.
The branch circuit overcurrent protection must be rated 27 A.
144
Specifications
Value
-40 VDC to -72 VDC
-48 VDC nominal input
22.1 A at -40 VDC input
18.2 A at -48 VDC input, nominal input
12.0 A at -72 VDC input
874 W at -40 VDC input
865 W at -48 VDC input, nominal input
854 W at -72 VDC input
2983 at -40 VDC input
2951 at -48 VDC input, nominal input
2912 at -72 VDC input
800 W at -40 VDC to -72 VDC
800 W at -40 VDC to -72 VDC
800 W at -40 VDC to -72 VDC input