Set
Function
value
Lower frequency
arrival
18
(Not output when
stopped)
Under voltage status
19
output
Communication
20
settings
21
Keep
22
keep
Zero speed running 2
23
(Also output when
stopped)
The accumulated
24
power-up time arrives
Frequency level
25
detection FDT2 output
Frequency 1 reaches
26
the output
Frequency 2 reaches
27
the output
Current 1 reaches the
28
output
Current 2 reaches the
29
output
30
Timed arrival output
31
AI1 enter the limit
32
Under load
33
Reverse run
34
Zero current state
Module temperature
35
arrives
36
Software current limit
When the operating frequency reaches the lower
limit frequency, the ON signal is output. In shutdown
mode, the signal is OFF.
When the inverter is in the undervoltage condition,
the ON signal is output.
Please refer to the communication protocol.
keep
keep
When the inverter output frequency is 0, the ON
signal is output. The signal is also on in the shutdown
state
When the accumulated time (P7-13) of the inverter
exceeds the set time of P8-16, the ON signal is
output.
Please refer to the description of function codes P8-
28 and P8-29.
Please refer to the description of function codes P8-
30 and P8-31.
Please refer to the description of function codes P8-
32 and P8-33.
Please refer to the description of function codes P8-
38 and P8-39.
Please refer to the description of function codes P8-
40 and P8-41.
When the timer function selection (P8-42) is valid,
the inverter will output the ON signal after the
running time reaches the set time.
When the value of analog input AI1 is greater than
P8-46 (AI1 input protection upper limit) or less than
P8-45 (AI1 input protection lower limit), the ON
signal is output.
When the inverter is in the under load state, the ON
signal is output.
When the inverter is running in reverse operation, the
ON signal is output
Please refer to the description of function codes P8-
28 and P8-29
The inverter module radiator temperature (P7-07)
reaches the set module temperature
When the arrival value (P8-47) is reached, the ON
signal is output
Please refer to the description of function codes P8-
36 and P8-37
- 90 -
description