8.2 Fault Display
When a fault occurs during running, the operation panel displays the fault code such as
shown in the following figure.
Fault
display
Over
current
FU02
during
acceleration
1. Increase the setting of P3-11 (V/F oscillation suppression gain)
by 10 gradually. The permissible maximum setting here is 100.
1. Decrease the setting of P3-01 (torque boost) by 0.5% gradually.
1. Increase the setting of P0-15 (carrier frequency) by 1.0 kHz
gradually. Note that increase in carrier frequency will result in an
increase in the leakage current of the motor.
1. Set rated motor voltage (P1-02) and rated motor frequency (P1-
04) correctly.
2. Decrease the setting of P3-01 (torque boost) by 0.5% gradually.
1. Ensure that P3-23 (voltage limit selection) is set to 1 (enabled).
Increase the setting of P3-24/P3-25 (frequency gain/voltage gain
for voltage limit) by 10 gradually. The permissible maximum
setting here is 100.
2. Decrease the setting of P3-22 (voltage limit 770v) by 10 V
gradually. The permissible minimum setting here is 700 V.
1. Increase the setting of P3-20 (93-20 factory default set 20) by 10
gradually. The permissible maximum setting here is 100.
2. Decrease the setting of P3-18 (P3-18 factory default is 150%) by
10% gradually.
The permissible minimum setting here is 50%.
Fault reason
Ground fault or short circuit
exists in
the output circuit.
Control mode is FVC or
SVC but motor auto-tuning
is not performed.
Acceleration time is too
short.
The over current stall
prevention
parameters are set
improperly.
Solution
Error settlement
Check whether short-circuit occurs
on the motor, motor cable or
contactor.
Set motor parameters according to
motor nameplate and perform motor
auto-tuning.
Increase acceleration time.
Ensure that current limit is enabled
(P3-19 = 1).
The setting of current limit level (P3-
18) is too large. Adjust it
between 120% and 150%.
The setting of current limit gain (P3-
20) is too small. Adjust it
between 20 and 40.
- 136 -