Download Print this page

Pentax DSI-200 Series User Manual page 139

Advertisement

Deceleration time is too
short.
Braking unit and braking
resistor are
not installed.
The over voltage stall
prevention
Over
parameters are set
voltage at
improperly.
FU07
constant
speed
An external force drives
motor during
running.
Pre-charge
Input voltage is not in
resistor
FU08
arranged range
fault
Instantaneous power failure
occurs
The AC drive's input
voltage is not
within the permissible
Under
range.
FU09
voltage
The bus voltage is
abnormal.
The rectifier bridge, the
buffer resistor, the drive
board or the control board
are abnormal.
Load is too heavy or
locked-rotor occurs on
AC drive
motor.
FU10
overload
The AC drive power class
is small.
P9-01 (Motor overload
protection gain) is set
improperly.
Motor
FU11
overload
Load is too heavy or
locked-rotor occurs on
motor.
Increase deceleration time.
Install braking unit and braking
resistor.
Ensure that the voltage limit function
is enabled (P3-23 )
The setting of voltage limit (F3-22)
is too large. Adjust it between 700 V
and 770 V.
The setting of frequency gain for
voltage limit (P3-24) is too small.
Adjust it between 30 and 50.
The setting of frequency rise
threshold during voltage limit (P3-
26) is too small. Adjust it between 5
Hz and 20 Hz.
Cancel the external force or install a
braking resistor
Arrange voltage in a reasonable range
Enable the power dip ride through
function (P9-59 ).
Adjust the voltage to normal range.
Contact the agent
Contact the agent
Reduce load or check motor and
mechanical conditions.
Replace a drive of larger power
class.
Set P9-01 correctly.
Reduce load or check motor and
mechanical conditions.
- 139 -