Running
frequency lower
P0-14
limit offset
Set range
When the frequency command is lower than the lower limit of P0-14, the inverter can be
stopped, run at the lower limit frequency or run at zero speed. What mode of operation can
be used through P8-14 (setting frequency lower than lower frequency operation mode) Set
up.
acceleration time 1 Factory default
P0-17
Set range
Deceleration 1
P0-18
Set range
The acceleration time refers to the time required for the frequency converter to
change from zero frequency to acceleration / deceleration reference frequency (P0-25),
see t1 in Figure 6-3. Deceleration time refers to the frequency converter from the
acceleration and deceleration reference frequency (P0-25 determined), deceleration to
zero frequency required time, see Figure 6-3
Figure6-3 acceleration/Deceleration time shows diagram
DSI-200 provides four groups of acceleration and deceleration time, the user can use the
digital input terminal S switch selection, four sets of acceleration and deceleration time
through the following function code settings:
Group one:P0-17、P0-18;
Group two:P8-03、P8-04;
Group three:P8-05、P8-06;
Factory
default
0.00Hz~upper frequency P0-12
0s~65000s(P0-19=0)
Factory
default
0s~65000s(P0-19=0)
- 64 -
0.00Hz