parameters through the communication value for the host computer monitoring. The
communication address is 0 × 7000 ~ 0 × 7040
Where d0-00 to d0-31 are the run and stop monitoring parameters defined in P7-03 and
P7-04.
d0-15
PID setting
d0-16
PID feedback
Display PID set value and feedback value, the value format is as follows:
PID setting = PID setting (percentage) * PA-04
PID feedback = PID feedback (percentage) * PA-04
Chapter 7 Fault Display and settlement
7.1 Guidance on the adjustment of the inverter before
commissioning
1) Drive in Open-loop Vector Control (P0-01=0)
The AC drive implements control of the motor speed and torque without an encoder for
speed feedback. In this control mode, motor auto-tuning is required to obtain the motor
related
Error
Overload or
Over current detected
during motor start
Poor torque or speed
response and motor
oscillation at speeds
below 5 Hz
Poor torque or speed
response and motor
oscillation at speeds
above 5 Hz
Low speed accuracy
Obvious speed
fluctuation
Display range
Display range
 Set motor parameters (P1-01~P1-05) according to motor
nameplate.
 Select a proper motor auto-tuning mode by setting P1-37 and
perform motor auto-tuning. If possible, select dynamic auto-
tuning
 1. If motor torque and speed response are too slow, increase
the setting of P2-00 (speed loop proportional gain 1) by 10
gradually or decrease the setting of P2-01 (speed loop
integral time 1) by 0.05 gradually.
 2. If motor oscillation occurs, decrease the setting of P2-00
and P2-01.
 1. If motor torque and speed response are too slow, increase
the setting of P2-03 (speed loop proportional gain 2) by 10
gradually or decrease. The setting of P2-04 (speed loop
integral time 4) by 0.05 gradually.
 2. If motor oscillation occurs, decrease the setting of P2-03
and P2-04.
If speed error when motor runs with load is large, increase
the setting of P2-06 (vector control slip compensation gain)
by 10% gradually.
If motor speed fluctuation is large, increase the setting of P2-
07 (SVC torque filter time) by 0.001s gradually.
- 134 -
0~65535
0~65535
0.00~320.0Hz(P0-22=1)
Solution