DRSQ38 Rear Venting

A maximum 18" of horizontal run is allowed on rear vented applications ,
though the addition of a 45° elbow is permitted for corner installations.
REAR VENTING NOT PERMITTED FOR 4/7 VENTING.
18'' Max. horozontal
run with no vertical lift
Hearth
Figure 9.b Straight run, Rear Vented, wall mounted termination.
45° Corner Installation 5''/8''
Attach an EEL-45 (45° elbow) directly onto the flue collar and attach it
to the EEL-45, cut the MXT-20 to suit. Slide the fireplace into position
and attach to the termination.
NOTICE
Corner Installation is available for NATURAL GAS UNITS ONLY
12
PXT20 Extention
Heat Sheild
Termination
18''
30½''
Max.
Termination
RHS 101 (5"8")
Heat Sheild
PXT20 (5"8")
PEL- 45 Elbow (5"/8")
Flue Collar
45° or less Corner Installation 5''/8''
Use an PTO-4 termination and an PFL-1 or PFL-2/PFL-2 (12" or 24"
compressed length) and a frame, if appropriate. Flex may be turned
to obtain desired degree of angle required but must not exceed 45°.
PVK05 kit can be also be used
NOTE: The PVK05 / PVK05F kit is available for top vent corner FLEX
application (NG only). The Kit includes a heat shield, flex pipe, and a
termination with or without a mounting frame.
Installation
Termination
RHS 101 (5"8")
Heat Sheild
Flex Section
Flue Collar
XG0230 - 052020