Symbols; Safety Measures & Warning - Goodwe NS Series User Manual

Solar inverter
Hide thumbs Also See for NS Series:
Table of Contents

Advertisement

1 Symbols

Failure to observe a warning indicated in this manual may result in
injury.
Recyclable materials
Danger of high voltage & electric shock
This side up - The package must always have the
arrows point up
Don't touch, hot surface!
6
No more than six (6) identical packages be stacked on each other.
Special disposal instructions
Fragile
Keep Dry
Refer to operation instructions
Wait at least 5 minutes after disconnecting the inverter before
touching internal parts
5min
CE mark.
01
2 Safety Measures & Warning
The NS/DNS series inverter of Jiangsu GOODWE Power Supply Technology Co, Ltd. (hereinafter
referred to as GOODWE) strictly conforms to related safety rules in design and test. Safety regula-
tions relevant to the location shall be followed during installation, commissioning, operation and
maintenance. Improper operation pose a risk of electric shock or damage to equipment and
property. (NS: Single-MTTP, Single-Phase, DNS Dual-MPPT, Single-Phase)
• Installation and connection of inverters must be performed by qualified personnel, in compli-
ance with local electrical standards, regulations and the requirements of local power authorities
and/or companies.
• To avoid electric shock, Dc input and AC output of the inverter must be disconnected for at least
5 minutes before performing any installation or maintenance.
• The temperature of some parts of the inverter may exceed 60c during operation. To avoid being
burnt do not touch the inverter during operation. Let it cool before touching it.
• Keep children away from inverter.
• Do not open the front cover of the inverter. Apart from performing work at the wiring terminal (as
instructed in this manual), touching or changing components without authorization may cause
injury to people, damage to inverters and annulment of the warranty.
• Static electricity may damage electronic components. Appropriate methods must be adopted to
prevent such damage to the inverter; otherwise the inverter may be damaged and the warranty
annulled.
• Ensure the output voltage of the proposed PV array is lower than the maximum rated inut voltage
of the inverter; otherwise the inverter may be damaged and the warranty annulled.
• When exposed to sunlight, the PV array generates dangerous high DC voltage. Please operate
according to our instructions, or it will result in danger to life.
• PV modules should have an IEC61730 class A rating.
• If the equipment is used in a manner not specified by the manufacturer, the protection provided
by the equipment's design may be impaired.
• To completely isolate the equipment: switch off the DC switch, disconnect the DC terminal, and
disconnect the AC terminal or AC breaker.
• Prohibit inserting or pulling the AC and DC terminals when the inverter is powered on.
• If there are more than 3 PV strings on input side, and additional fuse installation will be suggest-
ed.
• An earthing photovoltaic system requires the connection of an Arc fault detector on DC side.
• The inverter can exclude the possibility of DC residual currents to 6mA in the system, where an
external RCD is required in addition to the build=in RCMU, type A RCD must be used to avoid
tripping.
02

Advertisement

Table of Contents
loading

Table of Contents