Cable Installation

Wire Gauge and Torque Specifications

Wire Gauge Requirements for the GT100E MS Combiner Box

Torque Specifications for the GT100E MS Combiner Box

152602
CAUTION
All wiring methods and wire gauges shall be in accordance with Local Electrical
Code. Take care to keep the wire bundles away from any sharp edges which may
damage wire insulation over time.
The following torque specifications are to be used on all electrical
interfaces made during installation of the GT100E MS Combiner Box.
One or multiple wires up to 300 mm2 can be connected to the GT100E
MS Combiner box. Follow local Electrical codes to determine the correct
wire gauge.
M10 Bolt
40.0Nm
M12 Bolt
54.0Nm
M16 Bolt
132.0Nm