Xantrex GT100E Owner's Manual page 34

Xantrex technology master/slave owner's manual gt100e
Table of Contents

Advertisement

Configuration
3–4
3. Click Send Configuration
4. Verify that the Present Inverter Data has the unit set as the Configured
Slave unit.
Important:
If the inverter's date (not the workstation's!) is odd then the
Inverter is OPERATIONAL SLAVE until midnight; if the date is even, the
Inverter is OPERATIONAL MASTER until midnight.
CAUTION
The Master/Slave configuration will only be activated after power is cycled on
the unit.
Important:
Verify that the date is the same on both the GT100E #1 and
GT100E #2. This will allow the daily role reversal option to function correctly.
Refer to the GUI Help menu for complete configuration instructions.