1 5 O P T I O N S

15 Options

ABB modular system is provided with several fea-
tures that allow for easy adaptation to the re-
quired sites conditions. Following the "field in-
stallable kits":
• Network interface cards (SNMP)
• Elevation kit
• Battery Temperature Sensor
15.1

Network interface card (SNMP)

15.1-1: Customer
interface slot SNMP
NOTE
15.1-2: SNMP
ABB offers network inter-
face cards to connect ABB
UPS system to the net-
work.
The network interface
card provides:
• Remote monitoring via
Web
• Environmental moni-
toring
• Extensive alarm han-
dling and dispatching
• Redundant UPS moni-
toring
• Integration into net-
work or building management system
To install the SNMP card please follow the in-
structions below:
The Simple Network Management Protocol
(SNMP) is a worldwide-standardized
communication-protocol. It is used to monitor
any device in the network via simple control
language. The UPS-Management Software also
provides its data in this SNMP format with its
internal software agent. The operating system
you are using must support the SNMP protocol.
THE OPERATIONS DESCRIBED IN THIS
CHAPTER MUST BE PERFORMED BY A
SERVICE ENGINEER OF THE
MANUFACTURER OR BY AN AGENT
CERTIFIED BY THE MANUFACTURER
ALL THE INPUT/OUTPUT PORTS ARE
CLASS 2 (SELV CIRCUITS). PLEASE
MAINTAIN SECURITY WHEN CONNECTING
TO OTHER DEVICES.
Some of the features are design to be installed
only during the assembling on the factory and for
a safety reasons cannot be added on the field:
• Manual Bypass
Please indicate these option features when plac-
ing an order.
We offer our software with SNMP functionality
for Novell, OS/2, all Windows running on INTEL
and ALPHA, DEC VMS, Apple.
Two types of SNMP interfaces with identical func-
tionality are available: an external SNMP-Adapter
(Box) and an internal SNMP-Card. Both can man-
age a parallel system (N modules) and return ei-
ther global values - which are consistent for the
whole parallel system - or specific values from the
single modules.
15.1-2
The adapter may be configured via Telnet, HTTP
15.1-1
(Web-Browser) or serial connection (Terminal).
For normal operation at least one network con-
nection (Ethernet) is required.
The SNMP adapter can be used, utilizing the RC-
CMD send function, for an automatic network
wide shut down or just for informing connected
users. The shutdown procedure can be initiated
on a low residual battery autonomy time (down-
time) or by a countdown timer which is started at
the beginning of the alarm. A shut down is there-
fore possible without extra input from the opera-
tor, and is fully software controlled.
107
External SNMP-Adapter
Internal SNMP-Card