WAGO-TO-PASS® 761
761-110 Telecontrol Module Compact
Pos : 33.18 /Serie 759 ( WAGO-Software)/T O-PASS Konfig urati onssoftware/Parametrier ung/Par ametrierung I/O D O @ 3\mod_1223559342687_21.doc x @ 23786 @ 3 @ 1
6.10.2

Digital Outputs

Select your TO-PASS
using the identifier. Select the output to be configured under the entry Digital
Outputs.
The parameters of the output are given on the right side. The input fields are
identical for all digital outputs:

Figure 22: Configuring the digital outputs

Table 25: Configuring the digital outputs

Settings
Activation text
Deactivation text
Turn-off time
Pos : 33.19 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 2.0.0
®
telecontrol module from the left side of the project tree
In this field enter the activation text for the output.
®
When the TO-PASS
an SMS it switches this digital input on and connects the DC
voltage available at terminal 37 to the corresponding output.
In this field enter the deactivation text for the output.
®
When the TO-PASS
an SMS it deactivates this digital output and disconnects the
DC voltage available at terminal 37.
In these fields select the turn-off time for the output in hours,
minutes and seconds.
If the digital output has been activated, it will remain active
for the time defined here and voltage remains applied at
terminal 37. When this time elapses, the output switches off
the voltage at terminal 37 automatically.
The maximum turn-off time is limited to "00:01:59" up to
Firmware Version FW 2.33.
Define a time of "00:00:00" hh:mm:ss to deactivate this
function. The output will then remain permanently activated
until the next deactivation message is received.
Commissioning
telecontrol module receives this text as
telecontrol module receives this text as
55