2.1.1.5 Technical Data
Module Specific Data
Number of outputs
Current consumption
Current consumption
(Power jumper contacts) max.
Switching voltage
Switching power
Switching current
Contact material
Mechanical life
Isolation
Internal bit width
Dimensions (mm) W x H x L
Weight
Standards and Regulations (cf. Chapter 2.2 of the Coupler/Controller Manual)
EMC-Immunity to interference (CE) acc. to EN 50082-2 (96)
EMC-Emission of interference (CE) acc. to EN 50081-1 (93)
Approvals (cf. Chapter 2.2 of the Coupler/Controller Manual)
WAGO-I/O-SYSTEM 750
I/O Modules
750-523 [1 DO AC 230 V 16 A/Relay 1a/Pot. free]
1 make contact
(internal)
5 mA
max
80 mAs (Pulsed current)
AC 440 V
max.
5 kVA
max.
AC 16 A
max.
AgSnO2
10
1.5 kV
*2.5 kV rated surge voltage
2 Bit In (Manual status, -)
2 Bit Out (DO, -)
24 x 64* x 100
* from upper edge of 35 DIN rail
ca. 110 g
UL
(UL508)
C
US
Conformity Marking
6
switching operations
(System/Field)*
eff.
overvoltage category III
• 11
Technical Data